3.
Connect wiring to contactor coils.
Connect the contactor coils to the
terminals on each RMC-2RO 2-channel
relay output modules as shown.
note: For large contactors (greater
than 80 A rating) connect R-C surge
suppressors (available as accessories
from the contactor supplier) across the
coil contacts to reduce large voltage
spikes which occur when contactor coils
are switched off.
4. Connect digital inputs (if specified in design).
If circuit breaker trip or power contactor
failure alarms are to be used, connect
them to the Digital Inputs Module.
Connect the first input to the left-side
terminals on the module and the second
input to the right-side terminals on the
module, as shown. 24 Vdc is supplied
internally, so no external power supply
is required.
– – +
DC
OK
OUT DC 24V 2A
22,5-28,5
V DC
DC
Power supply
OK
(typical)
IN AC 100-240V
L(+) NC NC N (–)
Note: Previous wiring omitted for clarity.
Warning: The digital inputs should be
connected to dry (voltage free) contacts
only. Do not connect any source of
voltage to the digital input or damage
will occur.
– – +
DC
OK
OUT DC 24V 2A
22,5-28,5
V DC
Power supply
DC
OK
(typical)
IN AC 100-240V
L(+) NC NC N (–)
Note: Previous wiring omitted for clarity.
Contactor 1
ON
TxD
RxD
D1 D2
24V 0V
CRC
D1 D2
IO/RN
IO/ER
2
4
6
8
Address x 1
1
3
5
7
9
x 10
750-400 750-612
Digital
input 1
R
ON
TxD
RxD
D1 D2
24V 0V
CRC
D1 D2
IO/RN
IO/ER
2
4
6
8
Address x 1
1
3
5
7
9
x 10
750-400 750-612
Contactor 2
K
K
K
V IN
15 16
L
L
L
L
L
N
N
N
N
N
750-512
750-512 750-600
Digital
input 2
R
V IN
15 16
L
L
L
L
L
N
N
N
N
N
750-512
750-512 750-600
Contactor
coil
7

Werbung

loading