Conditions of use
Observe the operating conditions for wa-
►
ter heating installations as defined in
DIN 18380 "VOB German Contract Proce-
dures for Building Services".
Maintain water quality as defined in VDI
►
2035 "Prevention of damage in water heat-
ing installations".
Observe the limitations for use in damp
►
rooms as defined in DIN 55900 "Coatings
for radiators".
Use radiator only in closed heating systems.
►
Store and transport radiator only in the
►
protective packaging.
►
Observe minimum clearances between ra-
diator and surrounding objects for air cir-
culation.
Complaints
Please contact the supplier.
►
Disposal
Packaging and any parts that are not need-
►
ed should be recycled or disposed of prop-
erly. Observe local regulations.
Technical features
•
Operating pressure: max. 10 bar
•
Test pressure: 1.3 x operating pressure
•
Flow temperature: hot water up to 110°C
(230°F)
Installation
Bracket installation (see Fig. 1–8)
Check fasteners for damage.
►
Prepare tools and fastening materials
►
(screws, washers and wall anchors). Use
only approved screws and wall anchors to
ensure the required load-bearing capacity
for the radiator (available separately from
the manufacturer).
Mark position for upper holes to be drilled:
►
–
For reference dimensions, see Fig. B.
Drill holes and insert wall anchors. Note
►
walling material.
Position, attach, align and secure brackets
►
based on the desired wall spacing.
►
Install lower locking screws. Ensure that
the wall anchor is flush with the front edge
of the bracket.
Attach sound-absorbing clips to all brack-
►
ets.
Attach lift restraints to the outer brackets.
►
Heater installation (see Fig. 9–10)
Protect radiator from damage
When installing, only remove protective
►
packaging at the fastening and connection
points.
Only remove protective packaging com-
►
pletely during final cleaning or prior to
commissioning.
Compact radiator connection
Unscrew painted blind plugs at the desig-
►
nated connection points.
Connect radiator with commercially avail-
►
able fittings upstream.
Tightly cap open connections with vent
►
plugs (top) and blind plugs.
Only existing blind plugs may be used on Ker-
mi steel panel radiators.
Valve radiator connection
Valve with factory pre-set k
facturer's data).
Vent plugs (top) and blind plugs are factory
►
pre-assembled.
Remove painted caps on the valve mount-
►
ings and dispose of, as they must not be
used as seals on the radiator.
Connect radiator with commercially avail-
►
able fittings upstream on the valve mount-
ings.
Special connections
See manufacturer's data.
►
Commissioning
Fill the radiator and vent the radiator. Risk
►
of scalding!
Check radiator and connections for leaks.
►
value (see manu-
V