Conditions of use

Observe the operating conditions for wa-
ter heating installations as defined in
DIN  18380 "VOB German Contract Proce-
dures for Building Services".
Maintain water quality as defined in VDI
2035 "Prevention of damage in water heat-
ing installations".
Observe the limitations for use in damp
rooms as defined in DIN  55900 "Coatings
for radiators".
Use radiator only in closed heating systems.
Store and transport radiator only in the
protective packaging.
Observe minimum clearances between ra-
diator and surrounding objects for air cir-
culation.
Complaints
Please contact the supplier.
Disposal
Packaging and any parts that are not need-
ed should be recycled or disposed of prop-
erly. Observe local regulations.

Technical features

Operating pressure: max. 10 bar
Test pressure: 1.3 x operating pressure
Flow temperature: hot water up to 110°C
(230°F)

Installation

Bracket installation (see Fig. 1–8)
Check fasteners for damage.
Prepare tools and fastening materials
(screws, washers and wall anchors). Use
only approved screws and wall anchors to
ensure the required load-bearing capacity
for the radiator (available separately from
the manufacturer).
Mark position for upper holes to be drilled:
For reference dimensions, see Fig. B.
Drill holes and insert wall anchors. Note
walling material.
Position, attach, align and secure brackets
based on the desired wall spacing.
Install lower locking screws. Ensure that
the wall anchor is flush with the front edge
of the bracket.
Attach sound-absorbing clips to all brack-
ets.
Attach lift restraints to the outer brackets.
Heater installation (see Fig. 9–10)
Protect radiator from damage
When installing, only remove protective
packaging at the fastening and connection
points.
Only remove protective packaging com-
pletely during final cleaning or prior to
commissioning.
Compact radiator connection
Unscrew painted blind plugs at the desig-
nated connection points.
Connect radiator with commercially avail-
able fittings upstream.
Tightly cap open connections with vent
plugs (top) and blind plugs.
Only existing blind plugs may be used on Ker-
mi steel panel radiators.
Valve radiator connection
Valve with factory pre-set k
facturer's data).
Vent plugs (top) and blind plugs are factory
pre-assembled.
Remove painted caps on the valve mount-
ings and dispose of, as they must not be
used as seals on the radiator.
Connect radiator with commercially avail-
able fittings upstream on the valve mount-
ings.
Special connections
See manufacturer's data.
Commissioning
Fill the radiator and vent the radiator. Risk
of scalding!
Check radiator and connections for leaks.
value (see manu-
V
5