Do not mount the units on metal surfaces
Do not mount the units near electrical wires,
electronic equipment such as PCs, TV sets,
microwave equipment, etc.
Do not mount the units in the vicinity of large metal
structures or other construction elements
with fine metal meshes like special glass or
special concrete
Commissioning the controller / transmitter REV23RF
1
Mounting
Remove the unit from its base by proceeding according to
Fig. A. For mounting, refer to Figs. B, C and D and "Siting
notes for the controller/transmitter"
2
Remove the battery transit tab
As soon as the battery transit tab is removed, the unit
starts to operate (also refer to Fig. F).
3
Configuration
3.1
Accessing the heating engineer level
The heating engineer level will be enabled by pressing
simultaneously the warmer and colder buttons and by
rolling the roller selector away from the display and then
toward the display (also refer to Fig. G).
3.2
Functions
3.2.1
Calibrating the sensor
After activating the heating engineer level, the CAL symbol
will flash. When pressing the roller selector, the room
temperature currently measured flashes and can now be
recalibrated by a maximum of ± 2 °C by rolling either
toward the display or away from it. To store the
recalibration, press the roller selector
(also refer to Fig.
).
3.2.2
Setpoint limitation
There are 2 setting choices available:
or
On the heating engineer level, change from the flashing
CAL symbol to the setpoint limitation symbol by rolling
toward the display (also refer to Fig.
Press to accept. 5...29 °C will flash (factory setting). Press
to accept or continue rolling.
Setting 16...29 °C will flash.
Press to accept.
3.2.3
Optimum start control
On the heating engineer level, change from the flashing
CAL symbol to the optimum start control symbols
by rolling twice toward the display
(also refer to Figs.
and
Press to accept.
Press to accept or continue rolling until you reach ½, 1 or
optimization OFF
CE1G2265xx
).
).
will flash (factory setting).
. Press to accept.
Wall mounting
3.2.4
Control mode
On the heating engineer level, change from the flashing
CAL symbol to the symbols of the various control modes
by rolling several times toward the display (also refer to
Fig.
).
Press to accept.
to accept or continue rolling toward the display to select
one of the following control modes:
, PID 6, PID 12 or
required control mode.
A description of the different control modes is given below
(also refer to Fig.
Self-learning, adaptive control:
Suited for all standard applications (factory
setting).
PID 12 Normal controlled systems:
For locations with normal temperature variations.
PID 6
Fast controlled systems:
For locations with significant temperature
variations.
Difficult controlled systems:
Proper on / off controller with a switching
differential of 0.5 C
3.2.5
Periodic pump run
This function protects the pump against seizing during
longer off periods. Periodic pump run is activated for a
minute every 24 hours at 12:00 (when pump run is
activated, the flame symbol
On the heating engineer level, change from the flashing
CAL symbol to the
the display (factory setting, periodic pump run off). Press to
accept.
will flash (factory setting). Press to accept or
continue rolling. The
will flash. Press to accept (also refer to Fig.
3.2.6
Heating / cooling mode
On the heating engineer level, change from the flashing
CAL symbol to the heating / cooling symbols by rolling
away from the display.
Press to accept. The
setting). Press to accept or continue rolling. The cooling
symbol
will flash. Press to accept
(also refer to Fig.
24.07.2002
(factory setting) will flash. Press
. Press to accept the
).
appears on the display).
symbol by rolling twice away from
symbol for periodic pump run on
heating symbol will flash (factory
).
min.
10 cm
).
7/20