The transducer fulfils all the essential requirements and
regulations concerning electromagnetic compatibility (EMC)
and safety (IEC 1010 resp. EN 61 010). It was developed and
is manufactured and tested in strict accordance with the
quality assurance standard ISO 9001.

4. Ordering information

DESCRIPTION
1. Mechanical design
Housing T24 for rail and wall mounting
2. Rated frequency
1) 50 Hz (60 Hz possible without
additional error; 16 2/3 Hz, additional
error 1.25 %)
2) 60 Hz (50 Hz possible without
additional error; 16 2/3 Hz, additional
error 1.25 %)
3) 16 2/3 Hz (not reprogrammable by
user, 50/60 Hz possible, but with
additional error 1.25 %)
3. Power supply
Nominal range
1) AC
90...110 V
2) AC
99...121 V
3) AC
207...253 V
4) AC
360...440 V
5) AC
450...550 V
6) AC
623...762 V
7) DC/AC 24... 60 V
8) DC/AC 85...230 V
4. Power supply connection
1) External connection (standard)
2) Internal from voltage input
Line 2: Not available for rated
frequency 16 2/3 Hz and applications
A15/A16/A24
Caution! The power supply voltage must
agree with the input voltage (Table 2)!
5. Test certificate
0) None supplied
D) With test certificate in German
E) With test certificate in English
6. Configuration
0) Basic configuration
9) Programmed to order
Line 0: Not available if the power supply
is taken from the voltage input
Line 9: The filled form W 2410 e must
be part of the order. If primary values
of measurands and meters are re-
quired you have to fill the form as
well.
MARKING
406 - 1
1
2
3
H
= 100 V
1
n
H
= 110 V
2
n
H
= 230 V
3
n
H
= 400 V
4
n
H
= 500 V
5
n
H
= 693 V
6
n
7
8
1
2
0
D
E
0
9

5. Technical data

Input
Waveform:
Sinusoidal
Rated frequency:
50, 60 or 16 2/3 Hz
Consumption [VA]
(at external power
supply):
Voltage circuit: U
Current circuit: ≤ I
Continuous thermal ratings of inputs
Current circuit
10 A 400 V
Voltage circuit
480 V single-phase AC system
831 V three-phase system
Short-time thermal rating of inputs
Input
Number
of
inputs
Current circuit 400 V single-phase AC system
693 V three-phase system
100 A
5
250 A
1
Voltage circuit 1 A, 2 A, 5 A
Single-phase
AC system
600 V
H
: 1.5 Ur
10
intern
Three-phase
system
1040 V
H
: 1.5 Ur
10
intern
PROFIBUS-DP (Bus interface RS-485)
Bus connections:
Screw terminals on terminals
15 to 21
Protocole:
PROFIBUS-DP EN 50 170
Protocol chip:
SPC 41
Transmission rate:
9,6 kBaud ... 12 MBaud
automatic baud rate recognition
Addresses:
126 (default), set via
Set_Slave_Address
Max. length of bus:
100 ... 1200 m (dependent on the
baud rate and cable type)
Interface:
RS 485, electrically insulated
(500 V)
Configuration
possibilities:
Locally from a PC, or via bus master
2
/ 400 kΩ
· 0.01 Ω
2
single-phase AC system
693 V
three-phase system
Duration
Interval
of
between two
overload
overloads
3 s
5 min.
1 s
1 hour
10 s
10 s
10 s
10 s
31