Tabelle 26: Standardwerte Für Frequenzumrichter-Konfiguration; Tabelle 27: Vfd Set-Up Parameters For Fixed Cooling Applications - Heraeus Light Hammer 6 Installations- Betriebs Und Wartungshandbuch

Uv strahlersystem
Inhaltsverzeichnis

Werbung

K6 Gebläse
Allen Bradley PowerFlex 4M Variable Speed
Controller
240 and 480 Volt Models
PARA METERS NOT LISTED BELOW USE THE DEFAULT VALUES OR ARE INACTIVE FOR THIS APPLICATION.
>
Programmed Parameter Values
P#
Function
d001
Output Frequency
d003
Output Current
d007
Fault 1 Code
P101
Motor NP Volts
P102
Motor NP Hertz
P103
Motor OL Current
P104
Minimum
Frequency
P105
Maximum
Frequency
P106
Start Source
P107
Stop Mode
P108
Speed Reference
P109
Accel time 1
P110
Decel Time 1
P111
Motor OL Retention
t211
Analog In 0-10V Lo
t212
Analog In 0-10V Hi
A403
S-Curve %
A409
Internal Freq
A418
Skip Frequency
A419
Skip Frequency Band
A424
DC Brake Time
A425
DC Brake Level
A434
Reverse Disable
A435
Flying Start En
A442
Current Limit
A444
Motor OL Select
A446
PWM Frequency
A450
Fault Clear
A452
Auto Restart Delay
A457
Maximum Voltage
A458
Program Lock
A461
Motor NO FLA
Tabelle 27: VFD Set-up Parameters for Fixed Cooling
Allen Bradley PowerFlex 4M Variable Speed
Controller
240 and 480 Volt Models
PARA METERS LISTED BELOW ARE FOR USE WITH FIXED COOLING OR RAPID CYCLE APPLICATIONS.
>
Programmed Parameter Values
P#
Function
P108
Speed Reference
A409
Internal Freq
130
Tabelle 26: Standardwerte für
Frequenzumrichter-Konfiguration
?
Default
Value
265 or
460
60 Hz
60 Hz
3.6 or
1.8
0 Hz
~25 Hz
60 Hz
~52 Hz
0
0
0
0
0
2
10 sec
4 sec
10 sec
2 sec
0
1
0%
<
26%
>
100%
<
42%
>
0%
0%
60 Hz
0 sec
5 sec
0.1
0.2
0
1
0
1
0
3.8
0
4 kHz
4.8 kHz
0
0
1 sec
480
230/460
0
0
1.8
Applications
?
Default
Value
0
1
60 Hz
?? Hz
Oktober 2014
* These parameters may require adjustment for individual
installation
Notes
LED Display
LED Display
LED Display
Low Voltage or High Voltage Drive Model
Maximum allowable motor frequency
Set to maximum allowable motor current
* Adjust as needed to achieve 0.2 Pa (0.8") irrad.
pressure at system standby
* Adjust as needed to achieve 1.0 Pa (4.0") irrad.
pressure at 100% power
(terminal block I/O #1)
Ramp to Stop
* 0-10 V analog input (See
Tabelle 27
applications)
Enables overload counter feature
Sets the analog input level for MINIMUM frequency (0-60%
power levels)
Sets the analog input level for MAXIMUM frequency (100%
power level)
* Used only for fixed speed applications (see
works in conjunction with A419 to set minimum blower speed
*adjust to obtain low power and standby lamp operation
O)
(~0.6" H
2
Drive rated Amps x 0.1
1 = Reverse Disable
1 = Allows drive to reconnect to a spinning motor
Setting value to 1 clears faults
Drive rated volts
Motor nameplate rated full load amps
* These parameters may require adjustment for individual
installation
Notes
Internal Frequency Control Mode
* Adjust air pressure using up/down arrows in Program Mode
for fixed speed
Tabelle
27)
©Heraeus-Light Hammer 6