3.2 Nominal data

M3G112-GA
Motor
Phase
3~
Nominal voltage / VAC 400
Nominal voltage
380 .. 480
range / VAC
Frequency / Hz
50/60
Method of obtaining
ml
data
-1
1600
Speed / min
Power consumption /W 980
Current draw / A
1.6
Min. ambient
-25
temperature / °C
Max. ambient
60
temperature / °C
ml = Max. load · me = Max. efficiency · fa = Free air
cs = Customer specification · ce = Customer equipment
Subject to change

3.3 Data according to ErP Directive

01 Overall efficiency
/ %
η
es
02 Measurement category
03 Efficiency category
04 Efficiency grade N
05 Variable speed drive
06 Year of manufacture
/ kW 1
P
09 Power consumption
ed
09 Air flow
q
/ m³/h 6630
v
09 Pressure increase total p
/Pa
sf
-1
10 Speed n / min
11 Specific ratio
*
12 Recycling/disposal
13 Maintenance
14 Additional components
*
Specific ratio = 1 + p
/ 100 000 Pa
fs
Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller
combination in a standardized measurement setup.
Operating instructions
Actual
Req. 2015
43.5
33.7
A
Static
49.8
40
Yes
The year of manufacture is specified on the
product's rating label.
218
1610
1.00
Information on recycling and disposal is
provided in the operating instructions.
Information on installation, operation and
maintenance is provided in the operating
instructions.
Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

3.4 Technical description

17.3 kg
Weight
Fan size
500 mm
Rotor surface
Painted black
Electronics housing
Die-cast aluminum, painted black
material
Blade material
Press-fitted sheet steel blank, sprayed
with PP plastic
Fan housing material
Sheet steel, pre-galvanized and coated
with black plastic (RAL 9005)
Guard grille material
Steel, coated with black plastic (RAL
9005)
Number of blades
5
Airflow direction
"A"
Direction of rotation
Clockwise, viewed toward rotor
Degree of protection
IP54
Insulation class
"B"
Moisture (F) /
F4-1
Environmental (H)
protection class
Installation position
Shaft horizontal or rotor on bottom
On rotor side
Condensation
drainage holes
Mode
S1
Ball bearing
Motor bearing
Technical features
- Output 10 VDC, max. 10 mA
- Alarm relay
- Integrated PID controller
- Motor current limitation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection
<= 3.5 mA
Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)
Electrical hookup
Via terminal box
Motor protection
Thermal overload protector (TOP)
internally connected
with cable
Variable
Protection class
I (with customer connection of protective
earth)
Conformity with
EN 61800-5-1; CE
standards
EAC; UL 1004-7 + 60730
Approval

Werbung