Product Information / Produktinformation A6150
Bearing Vibration Monitor
1.7

Technical data

Only information with tolerances and limit values are considered as binding data. Data without
tolerances or error limits are provided as information only. We reserve the right to make technical
changes − particularly to the software.
All of the following information applies uniformly for channel 1 and channel 2, if not specified
otherwise.

1.7.1 Signal conditioning

Two separate signal inputs for channel 1 and channel 2 with uncoupled signal conditioning.
Measured value inputs
Differential voltage amplification inputs, non−reactive, open−circuit and short−circuit proof.
Channel 1
Channel 2
Input nominal range
Limit range
Input resistance
Frequency range
Signal conditioning
Sensor signal outputs
Channel 1 − SENS 1
Channel 2 − SENS 2
Signal output
Precision
Frequency range
Per. load resistance
Internal resistance
*Depends on the jumper setting J2.
z8: AIN1 (+);
z10: AIN1 (−)
d8: AIN2 (+);
d10: AIN2 (−)
−5 ... +15 V DC
± 30 V DC
> 100 kΩ
0.2 Hz ... 200 Hz (−3dB)
Front sockets SMB and/or z14 / z16*, decoupled,
open circuit and short circuit proof, non reactive.
SMB K1
SMB K2
±10 V; dynamic part of sensor signal (DC− filtered)
±1
of f.s.d.
%
0.2 ... 200 Hz (−3 dB) ±20 %
> 100 kΩ
1 kΩ