Roth Basicline H, i Bedienungsanleitung Seite 2

Raumthermostat

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Room thermostat Basicline H, i
manual
1. Application
The electronic Basicline H, i room thermostat for the room
temperature-dependent regulating of heating equipment is
designed for use in dry closed areas.
2. Function
The internal temperature sensor measures the room tempera-
ture. The output is triggered when the room temperature falls
below the set setpoint.
An input allows the setpoint to be lowered using a suitable
control device (clock thermostat) or an external clock.
2.1 Heating
The output is triggered when the room temperature falls below
the set setpoint. The active lowering reduces the setpoint by
approximately 2 K.
3. Installation — only by authorized trained personnel
Connection errors can cause damage to the automatic
control device!
No responsibility will be taken for any damage resulting
from the incorrect connection and/or improper use!
>
The device must be disconnected from the mains before
any work is done on it.
>
Only authorized trained personnel may make the connec-
tion and perform service!
>
The connection must be made using the accompanying
block diagram.
>
At the Basicline H, i 230 V must not be connected
devices with saftety extra-low (SELV) voltage.
>
At the Basicline H, i 24 V must not be connected
devices with 230 V voltage.
>
The same phase must be used for the power supply
(terminal 2) and the lowering (terminal 5).
>
The device is designed only for connection to permanent
wiring in dry closed areas.
>
The VDE 0100, EN 60730 (Part 1) and the regulations of
the local power utility company must be observed.
>
The automatic control device must be installed so that it
measures the average room temperature (avoid the
vicinity of inlet and outlet channels, windows and doors).
Install on interior walls approximately 1.3 to 1.5 m above
the floor (avoid direct sunshine).
If the device does not function, first check the correct
connection and the power supply.
3.1 Setting the desired temperature
The internal potentiometer À
is used to set the desired
room temperature to a value
within the range
5 °C to 30 °C.
4. Technical data
Type:
Temperature range:
Sensor tolerance:
Switching difference:
Sensor:
Desired temperature setting:
Operating voltage:
Basicline H, i 230 V
Basicline H, i 24 V
Output:
Maximum permitted
switching current:
Basicline H, i 230 V
Basicline H, i 24 V
Electrical connections:
Method of operation:
Impulse voltage withstand level:2.5 kV
Pollution degree:
Perm.ambient temperature:
Housing:
Dimensions:
Mounting:
Cable routing:
Degree of protection:
Safety class:
Weight:
5. Dimensions
6. Connection diagram
Subject to change without prior notice
Basicline H, i
+5 to + 30 °C
±1 K
±0.2 K fixed
Internal KTY semiconductor
sensor
internal potentiometer
230 V AC / 50 Hz (±10 %)
24 V AC / 50 Hz (20-30 V AC)
Triac output with potential
0.8 A, 230 V AC
(resistive/max. 5 actuators)
0.8 A, 24 V AC
(resistive/max. 5 actuators)
Screw terminals
1.C (no limiter method of
operation)
2
0 to +40 °C
Material Upper part ABS/PC
(impact- resistant,
flame-protected)
Lower part: PA6 GF30
81 x 81 x 16 (25) mm
With flush-mounting box
Through flush-mounting box
IP 30
II
Approx. 90 g