SD card
Note
SD card either for automatic backup or for data storage
The HMI device has a slot for an SD memory card. You can use the SD memory card either for automatic backup or for data
storage, e.g. for archiving.
The "automatic backup" and "archiving" functions cannot be used at the same time on the SD memory card.
Installed programs
NOTICE
HTML browser
The HTML browser cannot be used.
Communication
NOTICE
Only use S7-12xx CPUs with firmware version ≥ 4.1.
If you are using an S7-12xx CPU in a PROFIsafe-based F-system, this CPU must have a firmware version ≥4.1.
Otherwise, faults in the PROFIsafe communication may occur.
NOTICE
Avoiding PLC STOP
The replugging a fail-safe HMI device without logoff can lead to a communication error message. To avoid a PLC STOP in
such cases, use the required organization blocks. You can find additional information in the following manual:
SIMATIC Programming with STEP 7 V5.5 (https://support.industry.siemens.com/cs/de/en/view/45531107)
Processing time of function blocks
The following table shows the run times of function blocks depending on the controller used
F_FB_KTP_Mobile (FB198) 190 μs
F_FB_KTP_RNG (FB199)
F_FB_KTP_Mobile (FB198)
F_FB_KTP_RNG (FB199)
F_FB_KTP_Mobile (FB198) 430 μs
F_FB_KTP_RNG (FB199)
F_FB_KTP_Mobile (FB198) 400 μs
F_FB_KTP_RNG (FB199)
Important notes on your device
A5E35655148-AB, 08/2015
CPU 1510SP F-1 PN CPU 1512SP F-1 PN
150 μs
300 μs
240 μs
CPU 1515F-2 PN
CPU 1516F-3 PN/DP
80 μs
35 μs
130 μs
55 μs
CPU IM151-8F
CPU IM151-8F
(as of V3.2)
340 μs
550 μs
420 μs
CPU 315F-2 PN/DP
CPU 315F-2 PN/DP (as of V3.1)
200 μs
510 μs
260 μs
CPU 1511F-1 PN
CPU 1513F-1 PN
160 μs
110 μs
260 μs
180 μs
CPU 1517F-3 PN/DP CPU 1518F-4 PN/DP
10 μs
5 μs
15 μs
7 μs
CPU IM154-8F
CPU IM154-8FX
(as of V3.2)
(as of V3.2)
180 μs
100 μs
250 μs
140 μs
CPU 317F-2 PN/DP
130 μs