Important notes on your device

Product Information

A5E35655148
Validity
This product information applies to the following HMI devices of the type Mobile Panels 2nd Generation:
● KTP700 Mobile, article number 6AV2125-2GB03-0AX0
● KTP700F Mobile, article number 6AV2125-2GB23-0AX0
● KTP900 Mobile, article number 6AV2125-2JB03-0AX0
● KTP900F Mobile, article number 6AV2125-2JB23-0AX0
This product information contains important notes on your HMI devices in connection with the associated system
components. These notes supplement the operating instructions for the HMI device and take precedence over statements in
the operating instructions, the release notes, and in the online help.
Important notes
Software required
Note
WinCC V13 SP1 Update 3 or higher required
You need one of the following software products to configure the Mobile Panels 2nd Generation:
WinCC Comfort V13 SP1 Update 3 or higher
WinCC Advanced V13 SP1 Update 3 or higher
Parameter assignment for the HMI device
Note
Adapt the PROFIsafe address of the HMI device before the project transfer
If the PROFIsafe address of the HMI device is not adapted via the Control Panel before the project transfer, no PROFIsafe
communication is possible between the HMI device and the controller.
Configure the PROFIsafe address of the HMI device via the Control Panel before the project transfer. The PROFIsafe
address in the Control Panel must correspond to the PROFIsafe address of the HMI device in the project.
Note
Internet settings reset to default values after reboot
After restarting the HMI device, the internet settings in the "Internet Options" dialog are reset to the default values.