Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens 3WN6 Betriebsanleitung Seite 28

Vorschau ausblenden Andere Handbücher für 3WN6:
Inhaltsverzeichnis

Werbung

Fixed-moun-
Draw-out
ted breaker
breaker
X
X
X
X
X
X
X
X
X
X
X
*) Caution - Safety device: Do not cancel without a permissibility check.
28
Disturbance
Guide rails cannot be pulled
out for fitting of a circuit-
breaker
Breaker cannot be moved
from the maintenance positi-
on into the disconnected po-
sition
When cranking from the dis-
connected into the test positi-
on, strong resistance is felt
immediately after leaving the
disconnected
When cranking from the dis-
connected into the test positi-
on, thr breaker does not move
throughout thr frist 8 turns
Crank cannot be fitted for
racking
Cubicle door cannot be
opened (door interlock as
accessory)
Cause
1. Shutter locked with one or
two padlocks
1. Racing-in mechanism of
breaker not in disconnected
position (note position indi-
cator)
2. Attempt made to fit breaker
with different rated current
in guide frame
3. Coding of breaker and
guide frame do not match
1. Breaker not pushed right
in, lateral latches not yet
engaged (Attention: danger
of destruction)
1. Not a fault
1. OFF push button not pres-
sed
2. Switchgear cabinet door not
completely closed
3. Crank hole closed by pad-
lock(s)
1. Closed breaker is locking
switchgear cabinet door
2. Breaker in connected posi-
tion
Remedy
Remove padlocks
Crank the mechanism into
disconnected position
Only insert circuit-breaker
with the same rated current
data as the guide frames
Only insert circuit-breaker
with the same rated current
data as the guide frames
Push breaker as far as the
stop into the disconnected
position; the latches at the
side must engage
Crank further
Press OFF pushbutton and
move slide simultaneously
to the right
Close switchgear cabinet
door
Remove padlock (s) *)
Open the breaker
Crank breaker into test or
disconnected position

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis