MULTILEVEL SENSOR
When AEROPAC wave receives CO
>600 ppm = 2; >800 ppm = 3; >1000 ppm = 4; >1500 ppm = 5; >2000 ppm = 6;
>2500 ppm = max.
PROTECTION SET
0 = AEROPAC wave can be operated locally.
2 = local operation is locked.
CONFIGURATION COMMAND CLASS
Operating hours counter
Read out operating hours (CONFIGURATION_GET).
Parameter Number = 1
Configuration Value 1 = RUNTIME_H_MSB
Configuration Value 2 = RUNTIME_H_LSB
Configuration Value 3 = RUNTIME_L_MSB
Configuration Value 4 = RUNTIME_L_LSB
Timer duration
Set ventilator run time in Timer mode to 1-1080
Read out ventilator run time (CONFIGURATION_GET).
Parameter Number = 2
Configuration Value 1 = TIMER_VALUE_H_MSB
Configuration Value 2 = TIMER_VALUE_H_LSB
Remaining timer time (can only be read out)
Read out remaining time in Timer mode
Parameter Number = 3
Configuration Value 1 = TIMER_REMAIN_H_MSB
Configuration Value 2 = TIMER_REMAIN_H_LSB

Timer mode

Set timer start/stop and timer repeat
Read out timer operating mode
Parameter Number = 4
8
7
6
1) When a value >1,080 is specified, the timer is set to 1,080 minutes.
2) When the timer repeat is enabled, the timer is restarted every 24 hours.
3) The unit's current timer mode (current operating mode and remaining timer time) can also be read out.
Last update: 7.2.2014
reports, it activates the following blower levels:
2
3)
(CONFIGURATION_GET).
2)
(CONFIGURATION_SET).
3)
(CONFIGURATION_GET).
5
4
Timer Repeat
0 = disabled; 1 = enabled
1)
min. (CONFIGURATION_SET).
3
2
AEROPAC
1
Timer
0 = stopp; 1 = start
38