34
Run time for cooling actuator with increase/
decrease actuator
35
Neutral zone for increase/decrease actuator 2%
36
Time in hours between exercise of heating
actuator
37
Time in hours between exercise of cooling
actuator
42
Select if setpoint or actual value is to be
shown on display, 0=Actual, 1=Heating set-
point, 2=Cooling setpoint, 3=Average value
of heating and cooling setpoint, 4=Only
setpoint adjustment
43
Highest permitted setpoint offset upwards
44
Highest permitted setpoint offset downwards
45
Preset operating mode:
1=Unoccupied, 2=Stand-by,
3=Occupied. Forced ventilation is not set in
Occupied mode
46
State operating mode by depressing Oc-
cupancy button for 5 sec:
0=Off, 1=Unoccupied. Forced ventilation is
not set in Occupied mode.
47
No function for this model
48
Min. flow at cooling output with regulating
state heat/cool when VAV-control is selected
49
Max. flow at cooling output with regulating
state heat/cool when VAV-control is selected
and heating is applied
50-55
No function for this model
56
Temperature compensation on AI1
57
Temperature compensation on UI1
58
Temperature compensation for internal
room sensor
59
Filter factor for analogue temperature inputs 0,2
60
State NO/NC digital input 1: 0=NO
(Normally open), 1=NC (Normally closed)
61
State NO/NC digital input 2: 0=NO
(Normally open), 1=NC (Normally closed)
62
State NO/NC universal input 1: 0=NO
(Normally open), 1=NC (Normally closed)
63
Manual/Auto heating output signal: 0=Off,
1=Manual, 2=Auto
120 s
64
Manual/Auto cooling output signal: 0=Off,
1=Manual, 2=Auto
65
Manual/Auto forced ventilation: 0=Off,
1=On, 2=Auto. Can e.g. be activated from a
23
central system for e.g. night cooling
66
Manual/Auto control of change-over mode:
23
0=Heating control, 1=Cooling control,
2=Automatic change-over depending on
0
analogue temperature sensor or digital
input
67
Heating output signal in manual mode
68
Cooling output signal in manual mode
3°C
69-73
No function for this model
3°C
74
Setpoint display at setpoint adjustment:
0=The offset is shown in the display, 1=The
3
active setpoint + offset are shown in the
display. HEAT or COOL is shown depen-
ding on whether the unit controls according
to the heating or cooling setpoint when you
1
enter the menu, 2=The heating setpoint
+ offset are shown in the display, 3=The
cooling setpoint + offset are shown in the
display
20
This product carries the CE mark.
For more information, see www.regincontrols.com.
0
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
0°C
www.regin.se, info@regin.se
0°C
0°C
0
1
0
2
2
2
2
0
0
0
RC-DTO
INSTRUKTION
SV
REGIO RC-DTO
i
Läs denna instruktion innan produkten
monteras och ansluts
Rumsregulator med display och utgångar för
två ventiler med trepunktsställdon
RC-DTO är en rumsregulator i Regio Mini-serien avsedd att styra
värme och kyla i efterbehandlingssystem. Den har fyra digitala utgån-
gar för styrning av två ventiler med trepunktsställdon (öka-minska),
samt display. Montage sker direkt på vägg eller eldosa. Regulatorn
har ej kommunikationsanslutning.
Tekniska data
Matningsspänning
18...30 V AC, 50...60 Hz
Egenförbrukning
2,5 VA
Omgivningstemperatur
0...50°C
Omgivande luftfuktighet
Max 90% RH
Lagringstemperatur
-20...+70°C
Display
Bakgrundsbelyst LCD
Inbyggd temperaturgivare
Typ NTC, mätområde 0...50°C,
mätnoggrannhet +/-0,5°C vid 15...30°C
Ingångar och utgångar
Se inkopplingsbilder och tabell nedan
Anslutningsplintar
Av hisstyp för kabelarea max 2,1 mm
Skyddsklass
IP20
Material hölje
Polycarbonat, PC
Vikt
110 g
Mått
95 x 95 x 28 mm
Närvaroknapp
ÖKA-knapp
MINSKA-knapp
Installation
Montera regulatorn på en plats med för rummet representativ tem-
peratur. Lämplig placering är ca 1,6 m över golvet, utan omgivande
hinder för luftcirkulation. Ta av ramen genom att trycka in låshaken i
nederkanten av kåpan med en skruvmejsel. Se figur 1.
2
4