Setpoint
In Occupied mode, the controller operates from a heating setpoint
(FS = 22°C), or a cooling setpoint (FS = 24°C) that can be changed
using the INCREASE and DECREASE buttons.
Pressing on INCREASE increases the current
0.5°C up to the max. limit (+3°C). Pressing on DECREASE decreases
the current
setpoint in steps of 0.5°C down to the min. limit (-3°C).
Switching between heating and cooling setpoints is done automatical-
ly in the controller depending on the heating and cooling requirement.
Choice of setpoint display, see parameter 74.
Frost protection
Independent of the operating mode, the heating control is forced on
when the room temperature drops below 8°C (FS). Return to normal
control occurs automatically when the room temperature exceeds
8°C.
Condensation detector
If there is condensation, the cooling control is blocked. Return to nor-
mal control occurs automatically when condensation ceases.
Display handling
Indications
The display has the following indications:
Forced ventilation
Changeable value
Setpoint
Indoor /
outdoor temp.
OFF: Unoc-
cupied (also
shows tempe-
rature) or Off
STANDBY: Standby
COOL/HEAT: Shows if the unit
indication
indication
controls according to the heating
(only OFF)
or cooling setpoint
SERVICE: Setting
parameters
Buttons
RC-DTO has the following buttons:
Occupancy button
When the Occupancy button is held depressed for more than 5
setpoint in steps of
seconds, the controller changes operating mode to "Shutdown" (Off/
Unoccupied), regardless of the current operating mode. Via the
display, you can configure which operating mode, Off or Unoccupied,
should be activated on "Shutdown". The factory setting is that Unoc-
cupied is activated.
If you press the Occupancy button for less than 5 seconds when the
controller is in operating mode Shutdown or the preset operating
mode, the controller changes to operating mode Bypass. If you press
the button for less than 5 seconds when the controller is in Bypass,
it changes operating mode to the Preset operating mode. After a
configurable time in Bypass (FS = 2 hours), the controller returns to
the preset operating mode.
INCREASE button
DECREASE button
Setting parameters
Change parameters
It is possible to set different parameter values in a parameter menu. The
parameter menu is accessed by simultaneously holding the INCREASE
and DECREASE buttons depressed for about 5 seconds and then pressing
the INCREASE button twice. The Service indication will be displayed.
First the display will show the parameter-number 1. Scroll between parame-
ters by using the INCREASE and DECREASE buttons.
Occupancy
Press the Occupancy button to select the desired parameter. The para-
indication
meter number will be replaced by the parameter value. The value can be
changed using the INCREASE and DECREASE buttons. If a button is held
depressed the value will start scrolling, first slowly and then with increasing
Current room tem-
perature in °C to
speed in 3-4 steps with 2-3 seconds between steps.
one decimal point
Acknowledge/Regret change
To acknowledge and store a set parameter value, press the Occupancy
Open window
button again, the display then returns to showing the parameter number.
To retrieve the original value, i.e. the value before change, press the IN-
CREASE and DECREASE buttons at the same time. The original value is
shown on the display.
Return to normal display
After a certain time, about 1 minute, or when the INCREASE and DECREASE
buttons are pressed at the same time while in the menu, the display returns to
the normal view.
Exit is shown on the display after the last parameter. The parameter menu
is exited by pressing the Occupancy button while in Exit. Pressing on
INCREASE goes to the first parameter and pressing on DECREASE goes
to the last parameter.
RC-DTO
Parameter number
The following parameters can be changed in the parameter menu:
Para-
Description
meter
number
1
Basic setpoint heating
2
Basic setpoint cooling
3
Neutral zone at Stand-by.
Heat sp. = Basic sp. heat - 3.
Cool sp. = Basic sp. cool + 3.
4
Heat setpoint at Unoccupied
5
Cooling setpoint at Unoccupied
6
Frost protection setpoint
7
P-band for room controller
8
I-time (s) for room controller
9
With a lower temperature on the analogue
Change-over input, the cooling function is
selected
10
With a higher temperature on the analogue
Change-over input, the heating function is
selected
11
Control states: 0=Heat, 1=Heat/Heat,
2=Heat or cooling via Change-over,
3=Heat/Cooling , 4=Heat/Cooling with VAV-
control and forced supply air, 5=Heat/Coo-
ling with VAV-control, 6=Cooling , 7=Coo-
ling/Cooling
12
Time in Bypass mode
13
Disconnect timer with occupancy/unoc-
cupancy
14
Switch on delay for occupancy
15
State connected sensor on AI1:
0=Internal sensor, 1=External room sensor
16
State connected sensor on UI1:
0=None, 1=Change-over digital, 2=Change-
over analogue
18
State connected sensor on DI2:
1=Window contact, 2=Condensation detec-
tor
20-21
No function for this model
29-32
No function for this model
33
Run time for heating actuator with increase/
decrease actuator
FS
22°C
24°C
3°C
15°C
30°C
8°C
10°C
300 s
18
22
3
120 min
10 min
0 min
0
2
2
120 s
3