thicker wooden material than the panel. If there are no boards behind the panel, the boards can also be
fastened on the panel.
7. The right- or left-handedness of the heater can be changed by installing it to the rack correspondingly. Make
sure the clip fastens in the hole properly
8. Lift the heater to the rack on the wall so that the fastening hooks of the lower part of the rack go behind the
edge of the heater body. Lock the edge of the heater onto the rack by a screw.
Figure 7: Fastening the heater on a wall (all dimensions in millimeters)
Electrical Connections
The heater may only be connected to the electrical network in accordance with the current regulations by an
authorised, professional electrician.
•
The heater is semi-stationarily connected to the junction box (figure 8: A) on the sauna wall. The junction box
must be splash-proof, and its maximum height from the floor must not exceed 500 mm.
•
The connecting cable (figure 8: B) must be of rubber cable type H07RN-F or its equivalent.
NOTE!
Due to thermal embrittlement, the use of PVC-insulated wire as the connecting cable of the heater is
forbidden.
•
If the connecting and installation cables are higher than 1000 mm from the floor in the sauna or inside the
sauna room walls, they must be able to endure a minimum temperature of 170 °C when loaded (for example,
SSJ). Electrical equipment installed higher than 1000 mm from the sauna floor must be approved for use in a
temperature of 125 °C (marking T125).
•
In addition to supply connectors, the BC heaters are equipped with a connector (P), which makes the control
of the electric heating possible (figure 10). Voltage control is transmitted from the heater when it is switched
on. The control cable for electrical heating is brought directly into the junction box of the heater, and from
there to the terminal block of the heater along a rubber cable with the same cross-section area as that of the
connecting cable.
•
When closing the cover of the connection box make sure that the upper edge of the cover is placed
correctly. If the upper edge is misplaced water can enter the connection box. Figure 8.