11 Anhang
– 43: ""No trigger signal""
– 44: ""EMI error""
– 113: ""Communication hardware fault"""
linearization type
– Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container
– "0: ""Linear""
– 1: ""User def""
– 20: ""Cylindrical lying container""
– 21: ""Spherical container"""
curve_points_1_10
– X and Y values for the user defined linearization curve
curve_points_11_20
– X and Y values for the user defined linearization curve
curve_points_21_30
– X and Y values for the user defined linearization curve
curve_points_31_33
– X and Y values for the user defined linearization curve
curve status
– Result of table plausibility check
– "0: ""Uninitialized""
– 1: ""Good""
– 2: ""Not monotonous increasing""
– 3: ""Not monotonous decreasing""
– 4: ""Not enough values transmitted""
– 5: ""Too many values transmitted""
– 6: ""Gradient of edge too high""
– 7: ""Values not excepted""
– 8: ""Table currently loaded""
– 9: ""Sorting and checking table"""
SUB_DEVICE_NUMBER
SENSOR_ELEMENT_TYPE
– 0: "non-specific"
display_source_selector
– Selects the type of value that is displayed on the indication-/adjustement-module
– "0: ""Physical value""
– 1: ""Percent value""
– 2: ""Lin percent value""
– 6: ""Out(AI1)""
– 7: ""Level""
– 8: ""Out(AI2)""
– 9: ""Out(AI3)"""
max_peak_sensor_value
– Holds the maximum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
– Write access resets to current value
min_peak_sensor_value
– Holds the minimum sensor value. Write access resets to current value. Unit derives from 'Sen-
sor_range.unit'
– Write access resets to current value
CAL_POINT_HI
84