English
13 Device information
1
Type and order code
2
Design
Heat source
2.1
Version
2.2
Controller
2.3
Thermal energy metering
2.4
Installation location
2.5
Performance level
3
Operating limits
3.1
Heating water flow/return
3.2
Cooling water flow
3.3
Air (heating)
3.4
Air (cooling)
1
4
Flow
/ sound
4.1
Heating water flow heat pump circuit / free compression
Nominal flow in accordance with EN 14511at A7 / W35...30
4.2
Minimum heating water flow heat pump circuit
4.3
Cooling water flow rate heat pump circuit / free compression
Nominal flow in accordance with EN 14511A35 / W18...23
Minimum cooling water flow rate
4.4
Sound power level according to EN 12102
outdoors at A7/W55
Normal operation / reduced operation (outdoors)
4.5
Sound pressure level at 10 m distance
Normal operation / reduced operation
4.6
Air flow, normal operation / reduced operation
4.7
Sound power level in accordance with EN 12102
indoors at A7/W55
4.8
Sound pressure level at a distance of 1 m, indoors
5
Dimensions, weight and filling quantities
4
5.1
Device dimensions
5.2
Weight outdoor unit / incl. packing
Weight indoor unit / incl. packing
5.3
Device connections for heating
5.4
Refrigerant/total filling weight
5.5
GWP value / CO
equivalent
2
5.6
Lubricant/total filling quantity
5.7
Volume of heating water in the outdoor unit
5.8
Buffer tank
Nominal volume
Max. permissible operating temperature
Max. permissible operating pressure
5.9
Indoor unit
Volume of heating water in the indoor unit
Heat exchanger area
Max. permissible operating temperature
Max. permissible operating pressure
5.10 Electrical pipe heater
5.11 Start-to-leak pressure, safety valve
EN-30
m³/h /Pa
at A7 / W45...40
m³/h / Pa
at A7 / W55...50
m³/h / Pa
m³/h / Pa
m³/h / Pa
m³/h / Pa
2 3
2
indoor unit
H x W x D mm
outdoor unit
H x W x D mm
Type / kg
Type / litres
452172.66.05-EN · FD 0503
LIA 0608HXCF M - LIA 1316HXCF M
LIA 0608HXCF M
Air
Split reversible
WPM Touch
Yes
Indoors/outdoors
Variable
° C
up to 65 / from 12
° C
7 to 25
° C
-22 to +35
° C
+10 to +43
1.07 / 8603
1.10 / 8898
1.04 / 7741
0.65 / 3336
1.07 / 10900
1.07 / 10900
58 / 53
dB(A)
30 / 25
dB(A)
m³/h
2770 / 2030
42
dB(A)
35
dB(A)
657 x 444 x 261
712 x 1008 x 426
kg
60 / 65.5
kg
31.9 / 36.2
mm
28
R32 / 1.5
--- / t
675 / 1.01
FW68S / 0.46
Litres
0
Litres
25
°C
75
bar
3
Litres
-
m²
-
°C
-
bar
-
5
kW
2, 4 or 6
bar
2.5
LIA 0911HXCF M
Air
Split reversible
WPM Touch
Yes
Indoors/outdoors
Variable
up to 65 / from 12
7 to 25
-22 to +35
+10 to +43
1.72 / 22533
1.72 / 22129
1.65 / 20082
1.07 / 8603
1.72 / 26300
1.72 / 26300
60 / 55
32 / 27
4030 / 2910
42
35
657 x 444 x 264
865 x 1118 x 523
78.5 / 92
31.9 / 36.2
28
R32 / 1.65
675 / 1.2
FW68S / 0.46
0
25
75
3
-
-
-
-
5
2, 4 or 6
2.5
www.dimplex.eu