3 Protection instructions
3.1 Compressor Protection
The minimum time before the compressor can restart after stopping is 3 minutes.
This 3 minute wait period is not required for:
- The first power on
- Within 3 minutes of powering off
- Within 3 minutes of powering back on after powering off
The only exception is within the 3 minutes before powering off.
After turning on, the compressor will run for at least 3 minutes. Even if conditions
for shut off are met, it will not shut off within the first 3 minutes unless the unit is
powering off. This protection ensures the compressor operates for a minimum
run time before each start/stop cycle.
3.2 Fail safe
Serial
The name of
number
the fault
Indoor ambient
temperature
failure
Note 1: To query faults, long press the wind speed key and - key for 2 seconds.
To exit fault query and resume normal display, long press the wind speed and -
keys again for 2 seconds. Fault information will be lost after a power failure and
need to be regenerated. Long pressing the wind speed and - keys for 2 seconds
will query and display any faults, showing multiple faults simultaneously in order
of priority if present.

3.3 Memory Function

1.,Enter standby mode before powering off, or set a timer-based shutdown
when powering on, then enter standby after powering on.
2. If power is turned on before powering off, it will resume operating in the
original mode, with the previously set temperature, wind speed, temperature
unit, water motor switch status etc. After powering off.
Failure
code
Fault description Troubleshooting Illustrate
Static
display
The sensor is
E1
open or shorted
The query
Stoppage
displays