Auto / Manual On and Off Provides
the following lighting options:
Automatic operation (S1 closed, S2
open) Manual operation - with S1
open, the lamp is manually controlled
by the use of S2.
SINGLE POLE
2 GANG SWITCH
S1
LIVE
S2
EARTH
NEUTRAL
Fig. 12
Multiple lamps More than one
light-fitting can be wired in parallel to
the detector using any of the above
switching methods. The combined
wattage of connected lighting must
not exceed the 'Maximum Switchable
Load' as given in the Technical
Specifications section.
INDOOR SWITCH
FOR PERMANENT
OFF OVERRIDE
(OPTIONAL)
L
LIVE
EARTH
NEUTRAL
Fig. 13
L
L1
N
LAMP
L1
N
LAMP
LAMP
LAMP
4
OPERATION &
TESTING
Walk testing
When the installation procedure is complete,
the unit is ready for testing.
The Walk Test procedure is as follows:
Step 1
Using a small flat bladed screwdriver, set
the two adjustment controls on the under-
side of the PIR to the following positions:
TIME
- Fully anti-clockwise
LUX
- Fully clockwise
LUX
With these settings, the unit will operate
during daytime as well as at night,
illuminating the floodlight for approx.
5 seconds each time movement is
detected. This allows testing to be carried
out following installation in order to establish
the best position for the sensor head,
ensuring optimum performance.
5
TIME
Fig. 14