Herunterladen Inhalt Inhalt Diese Seite drucken

Maintenance - Honeywell MiniPlus FF06 Installationsanleitung

Vorschau ausblenden Andere Handbücher für MiniPlus FF06:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1

8. Maintenance

We recommend a planned maintenance contract with
an installation company
In accordance with DIN 1988, part 8, the following measures
must be taken:
8.1. Inspection
8.1.1. Rinse filter
Frequency: at least every 2 month (depending on local
operating conditions
• Non-compliance can lead to the filter becoming
blocked This results in a drop in pressure and
decreasing water flow
• The filter meshes are made of stainless steel. A red
coating as a consequence of rust from the pipelines
has no influence on function or the way the filter
works
To be carried out by an installation company or the
operator.
Filtered water can be drawn during rinsing.
If rinsing is into a container, then a suitable container
must first be put underneath.
1. Open the ball valve by turning the rinse knob
• Rinse knob must be vertical
2. Close the ball valve after approximately 15 seconds
A longer reverse rinse period may be necessary if the
filter is very dirty (Replace filter mesh see Servicing)
8.2. Maintenance
8.2.1. Replace filter mesh
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
• Use double ring wrench ZR06F
5. Remove filter cartridge
6. Remove filter insert
7. Replace filter mesh
8. Mount the filter insert
9. Re-insert the filter insert
10. Put O-ring on filter bowl
11. Screw filter bowl in place
12. Slowly open shutoff valve on inlet
13. Slowly open shutoff valve on outlet
MU1H-1115GE23 R1111
GB
8.3. Cleaning
Caution !
Do not use any cleaning agents containing solvents
and/or alcohol to clean the plastic parts!
If necessary, the filter bowl and the filter can be cleaned.
Frequency: at least every 2 month (depending on local
operating conditions
• Non-compliance can lead to the filter becoming
blocked This results in a drop in pressure and
decreasing water flow
• The filter meshes are made of stainless steel. A red
coating as a consequence of rust from the pipelines
has no influence on function or the way the filter
works
To be carried out by an installation company or the
operator.
Detergents must not be allowed to enter the environ-
ment or the sewerage system!
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Unscrew filter bowl
• Use double ring wrench ZR06F
5. Remove filter cartridge
6. Remove filter insert
7. Clean sieve
8. Clean filter bowl
9. Mount the filter insert
10. Re-insert the filter insert
11. Put O-ring on filter bowl
12. Screw filter bowl in place
13. Slowly open shutoff valve on inlet
14. Slowly open shutoff valve on outlet
9. Disposal
• Body of dezincification resistant pressed brass
• Brass threaded connections
• Stainless steel fine filter
• Red-bronze or shock-resistant, clear transparent synthetic
material filter bowl
Observe the local requirements regarding correct waste
recycling/disposal!
6
Honeywell GmbH

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Miniplusff06-aam

Inhaltsverzeichnis