10. Operation

10.1.Changing time raw water hardness and resi-
dual water hardness
1. MENU / OK
• Display Current time flashes
2. Continue with point 2 to 7 chapter 10.2
No regeneration needs to be carried out.
10.2.Initiating a manual regeneration
It is possible to initiate a manual regeneration (within the
4-day interval). The manual regeneration is carried out
immediately.
1. Press the REGENERATION key for 5 seconds
• Display Regeneration active flashes
REGENERATION AKTIV
• After completion of the regeneration, the device returns
automatically to the normal operating mode
If the water was switched off for a longer period (more
than 4 days), it is recommended to carry out a manual
regeneration after re-establishing the water supply.
10.3.Refilling salt tablets
Check the salt supply (e.g. monthly) in the device
Use only salt tablets acc. DIN 19604.
1. Open the salt container cover
2. Refill salt
10.4.Further information
10.4.1.Power Failure:
Brief power failure:
All settings including the time remain intact
After longer power outage:
• Display Current time flashes
• Continue with point 2 to 11 chapter 10.2
The settings, excluding the time remain intact, but need
to be confirmed with MENU / OK .
The regeneration needs to be carried out to return to the
normal operating mode.
MU1H-1417GE23 R1114
GB

11. Maintenance

11.1.Maintenance
In compliance with European and national norms (e.g.
DIN 1988 part 8) regular maintenance must be conducted.
Maintenance work should only be carried out be quali-
fied staff!
• Please contact your professional plumber or
Honeywell's technical customer services.
Interval: yearly
The completed maintenance work needs to be docu-
ments in the maintenance log (chapter 17).
Service tasks are described in the separate mainte-
nance instructions. These instructions are delivered
together with the spare parts.
The following maintenance work needs to be carried out:
11.1.1.Replace disinfection unit
For replacement, the disinfection unit DE10S-A (for
devices up to July 2013) or the new disinfection unit
DE10S-AN (for devices after August 2013) is needed.
The service lives of the disinfection units are as follows:
DE10S-A: 100 regeneration (approx. 1 year)
DE10S-AN: 400 regeneration (approx. 4 years)
After this, they must be replaced.
11.1.2. O-rings of the ejector
To replace the O-rings at the ejector, the maintenance
set EK10S-C is needed.
11.1.3. Suction pump
The following maintenance sets are required for mainte-
nance on the ejector:
EK10S-B (for devices up to July 2013) with red nozzle
holding element or
EK10S-BN (for devices from August 2013) with white
nozzle holding element
EK10S-B and EK10S-BN outwardly vary in the colour of
the nozzle holding element (see above).
11.1.4. Seal kit for controller head
The controller head seal kit EK10S-A is needed for the
replacement.
11.2.Cleaning
Do not use cleaning agents that contain solvents when
cleaning the plastic parts!
Detergents must not be allowed to enter the environ-
ment or the sewerage system!
1. Clean the housing with water and a cloth inside and out

12. Disposal

• High quality synthetic material housing
• All components subject to pressure in glass-fibre-rein-
forced plastics
• All components to brine in Noryl
Observe the local requirements regarding correct waste
recycling/disposal!