ATTENTION
Leaking connection due to failed pressing sequence
▶ Make sure that the pressing collar is completely closed after
the pressing sequence.
▶ Have any Geberit pressing collars that have not been closed
completely, as well as the adapter jaw and pressing tool,
inspected by an authorised repair shop.
▶ Replace any connections that have not been pressed
correctly. They must not be pressed again.
▶ If there are any burrs on the pressfitting after the pressing
procedure, have the pressing collar and the adapter jaw tested
by an authorised repair shop.
10
Open the Geberit adapter jaw and remove it from the Geberit
pressing collar.