For installation and set-up follow the instructions on the use in
hazardous areas.
Function and features
The AS-i module operates as a slave in the AS-i network (AS-i profile:
S-8.0.E). It connects four actuators (10 ... 30V DC) with the AS-i master.
• maximum number of modules per master: 31
• operating voltage 26.5 ... 31.6V
• external power supply to PELV
• current consumption <50mA
• voltage range 24V DC (15 ... 30V DC)
• max. current load per output (DC13)* 1A (typ.), 2A per module
• AS-interface version 2.1
*
Utilisation category (DC13): The switch-on and switch-off capacity for the triggering of solenoids is rated up
to 20W (to IEC 947-5-2).