Herunterladen Diese Seite drucken

Tecsis P3298 Betriebsanleitung Seite 21

Vorschau ausblenden Andere Handbücher für P3298:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7. Starting, operation
Electrical connection
Connect the instrument to earth via the pressure connection.
Operate the pressure sensor with a shielded cable and earth the shield at least on one
side of the cable, if the cable is longer than 30m (2-wire) or 3m (3- or 4-wire), or if it is
run outside of the building.
Use power supplies which guarantee reliable electrical isolation of the operating
voltage as per IEC/DIN EN 60204-1. Consider also the general requirements for PELV
circuits in accordance with IEC/DIN EN 60204-1.
Ingress protection per IEC 60529 (The ingress protection classes specified only apply
while the pressure sensor is connected with female connectors that provide the
corresponding ingress protection).
Ensure that the cable diameter you select fits to the cable gland of the connector.
Ensure that the cable gland of the mounted connector is positioned correctly and that
the sealings are available and undamaged. Tighten the threaded connection and check
the correct position of the sealings in order to ensure the ingress protection.
Please make sure that the ends of cables with flying leads do not allow any ingress of moisture.
Electrical connections
2-wire
3-wire
Wire gauge
Diameter of cable
Ingress protection per IEC 60 529 IP 65
Betriebsanleitung/Operating instructions/Mode d'emploi/Instrucciones de servicio
L-connector DIN
175301-803 A
UB = 1 0V = 2
UB = 1 0V = 2 S+ = 3
up to max. 1.5 mm 2
6-8 mm
The ingress protection classes specified only apply while the pressure sensor is
connected with female connectors that provide the corresponding ingress protection.
Circular connector
M12x1
UB = 1 0V = 3
UB = 1 0V = 3 S+ = 4 UB = brown 0V = green S+ = white
-
-
IP 67
Flying leads
UB = brown 0V = green
0.5 mm 2 (AWG 20)
6.8 mm
IP 67
GB
21

Werbung

loading