Mounting the module with input bus connector
6
Mounting the module with input bus connector
6
2)
For remote rows of modules, install the 2nd 800-
For remote rows of modules, install the 2nd 800-
CON transfer module from the set with input bus
y,
CON transfer module from the set with input bus
ATTENTION
ATTENTION
connector when the system is de-energized:
connector when the system is de-energized:
Incorrect assembly of the data cable can destroy
Incorrect assembly of the data cable can destroy
your basic device with modules or your system!
your basic device with modules or your system!
ng
A defective or incorrectly assembled data cable
A defective or incorrectly assembled data cable
between the transfer modules can lead to
between the transfer modules can lead to
destruction of your basic device and your modules
destruction of your basic device and your modules
and thus to property damage.
and thus to property damage.
· Use a data cable with a 1:1 line connection for
· Use a data cable with a 1:1 line connection for
the connection between the transfer modules!
the connection between the transfer modules!
· Always connect your transfer modules via
· Always connect your transfer modules via
shield terminals with tension relief!
shield terminals with tension relief!
Bottom
Bottom
· Protect your system against overvoltages and
· Protect your system against overvoltages and
bolts
bolts
electromagnetic disturbances by connecting
electromagnetic disturbances by connecting
the data cable shield to the shield terminal!
the data cable shield to the shield terminal!
ATTENTION
ATTENTION
Improper handling or rough handling can destroy
Improper handling or rough handling can destroy
your devices and modules!
your devices and modules!
Contacts, bottom bolts and retaining clips can
Contacts, bottom bolts and retaining clips can
be damaged or broken off during assembly/
be damaged or broken off during assembly/
disassembly.
disassembly.
· Never touch or manipulate the contacts!
· Never touch or manipulate the contacts!
· Protect contacts during handling,
· Protect contacts during handling,
transportation and storage!
transportation and storage!
· Never use force to assemble/disassemble
· Never use force to assemble/disassemble
devices/modules!
devices/modules!
· If necessary, observe further usage information
· If necessary, observe further usage information
on the devices, modules and components of
on the devices, modules and components of
your measuring device and module topology.
your measuring device and module topology.
":
Fig.: Module 800-CON - rear view (with input bus connector)
Fig.: Module 800-CON - rear view (with input bus connector)
9
9
Dismounting
Dismounting
Dismounting the transfer module 800-CON:
Dismounting the transfer module 800-CON:
1. Disconnect the system from the power supply! Secure
1. Disconnect the system from the power supply! Secure
it against being switched back on! Verify disconnection
it against being switched back on! Verify disconnection
from power! Ground and short circuit! Cover or block off
from power! Ground and short circuit! Cover or block off
neighboring parts that are under voltage!
neighboring parts that are under voltage!
2. Disconnect the wiring and the terminal.
2. Disconnect the wiring and the terminal.
3. Remove or shift the shield terminal and end brackets of
3. Remove or shift the shield terminal and end brackets of
your series of devices and modules.
your series of devices and modules.
4. Decouple the bus connector (JanBus interface) of
4. Decouple the bus connector (JanBus interface) of
the transfer module from the basic device and/or the
the transfer module from the basic device and/or the
connected module by pulling it out.
connected module by pulling it out.
5. Unlatch the bottom latches of the transfer module.
5. Unlatch the bottom latches of the transfer module.
Recommendation: Use a screwdriver for this
Recommendation: Use a screwdriver for this
(carefully!).
(carefully!).
6. Remove the DIN rail from the transfer module without
6. Remove the DIN rail from the transfer module without
touching or damaging the bus connector contacts.
touching or damaging the bus connector contacts.
ATTENTION
ATTENTION
Handling your module too roughly may cause
Handling your module too roughly may cause
damage to the module and result in property
damage to the module and result in property
damage!
damage!
The bus connector contacts and the bottom latches
The bus connector contacts and the bottom latches
can be damaged or broken off during dismantling of
can be damaged or broken off during dismantling of
your module.
your module.
· Never wrench the module from the DIN rail
· Never wrench the module from the DIN rail
using force.
using force.
· Decouple the bus connector (JanBus interface)
· Decouple the bus connector (JanBus interface)
beforehand and carefully unlatch the bottom
beforehand and carefully unlatch the bottom
latch of the module using a screwdriver!
latch of the module using a screwdriver!
1. Press in the open bottom bolts on the rear of
1. Press in the open bottom bolts on the rear of
the module.
the module.
ATTENTION
ATTENTION
2. If not already done, plug the input bus
2. If not already done, plug the input bus
Modules are not recognized by the basic device
Modules are not recognized by the basic device
connector (JanBus interface) included in the
connector (JanBus interface) included in the
during the startup process!
during the startup process!
scope of delivery into the sockets on the back
scope of delivery into the sockets on the back
If there is no communication to the modules, the
If there is no communication to the modules, the
of the module.
of the module.
module functions are not supported (e.g. current
module functions are not supported (e.g. current
measurements).
measurements).
· Disconnect your system from the power supply
· Disconnect your system from the power supply
and check the condition of the bus connector
and check the condition of the bus connector
and the connections of your modules to the
and the connections of your modules to the
basic device (JanBus interface). If necessary,
basic device (JanBus interface). If necessary,
slide the contacts of the module bus connector
slide the contacts of the module bus connector
Input bus
Input bus
Input bus
Input bus
into the sockets of the basic device bus
into the sockets of the basic device bus
connector
connector
connector,
connector,
connector or the connected modules so that
connector or the connected modules so that
rotated
the bus connectors (devices) are linked.
rotated
the bus connectors (devices) are linked.
· For spatially separated series of modules,
· For spatially separated series of modules,
check the connection of the transfer modules
check the connection of the transfer modules
with the connection via the shield terminals.
with the connection via the shield terminals.
· If necessary, restart the basic device.
· If necessary, restart the basic device.
· If the specified measures are unsuccessful,
· If the specified measures are unsuccessful,
please contact our support team -
please contact our support team -
www.janitza.com
www.janitza.com
Screwdriver for
Screwdriver for
unlatching
unlatching
Bus connector
Bus connector
contacts
contacts
JanBus
JanBus
interface
interface
Bus connector
Bus connector
sockets
sockets
Bottom latch
Bottom latch
Fig.
Fig.
Terminal
Dismounting the
Dismounting the
transfer module
transfer module
ATTENTION
ATTENTION
Property damage due to dismantling or
Property damage due to dismantling or
decoupling the module during operation!
decoupling the module during operation!
Dismantling or decoupling the module while it is
Dismantling or decoupling the module while it is
communicating with the basic device can lead to
communicating with the basic device can lead to
damage to your devices!
damage to your devices!
· Disconnect your system from the power supply
· Disconnect your system from the power supply
before dismantling or decoupling the module!
before dismantling or decoupling the module!
Secure it against being turned back on! Verify
Secure it against being turned back on! Verify
disconnection from power! Ground and short
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
circuit! Cover or block off neighboring parts that
are under voltage!
are under voltage!
Example of a measuring device and module topology with the
8
8
3. Press the 2nd transfer module with input bus
3. Press the 2nd transfer module with input bus
800-CON transfer modules (set of 2)
connector onto the DIN rail until the bottom bolts
audibly engage.
4. Mount further modules (e.g. current measu-
4. Mount further modules (e.g. current measu-
ring modules, digital input modules) and push
their contacts into the sockets of the input bus
connector so that the devices are coupled to the
transfer module 800-CON.
Press the bus
Press the bus
connector
connector
contacts of the
contacts of the
input bus
input bus
connector into
connector into
the module
the module
sockets
sockets
click!
Example: Mounting of the 800-CON transfer module with input bus connector of the remote measuring
point
Example of a measuring device and module topology.
Technical data
10
10
Bottom latch
Bottom latch
General information
Net weight
(with plug terminals)
DIN rail
Device dimensions
DIN rail
Width of the device in
horizontal pitches (HP)
Installation position
Mounting/assembly -
suitable DIN rails -
35 mm (1.38 in)
Protection class
Operating temperature
Impact resistance
Transport and storage
Terminal
The following information applies to devices which are
transported and stored in the original packaging
Free fall
Temperature
Relative humidity
Ambient conditions during operation, see basic device
Interface
JanBus (proprietary)
10 / 10
Example of a measuring device and module topology with the
5. Check the fit of your device and module series
800-CON transfer modules (set of 2)
and mount end brackets.
connector onto the DIN rail until the bottom bolts
6. Finally, wire your series of measurement devices
audibly engage.
and modules, observing the usage information
for all integrated devices and modules.
ring modules, digital input modules) and push
7. Apply voltage to the basic device (system). The
their contacts into the sockets of the input bus
basic device detects the modules automatically.
connector so that the devices are coupled to the
transfer module 800-CON.
800-CON module with
800-CON module with
input bus connector
input bus connector
End bracket
Sockets of
Sockets of
the input bus
the input bus
connector
connector
Bottom bolt
Bottom bolt
click!
DIN rail
DIN rail
DIN rail
Example: Mounting of the 800-CON transfer module with input bus connector of the remote measuring
point
Example of a measuring device and module topology.
Technical data
Terminal connection capacity
General information
Connectable conductors.
Net weight
Approx. 55 g (0.12 lb) - 1 device
Approx. 55 g (0.12 lb) - 1 device
Only one conductor can be connected per terminal.
(with plug terminals)
approx. w = 18 mm (0.71 in),
Single core, multi-core,
approx. w = 18 mm (0.71 in),
h = 90 mm (3.54 in),
fine-stranded
Device dimensions
h = 90 mm (3.54 in),
d = 76 mm (2.99 in)
d = 76 mm (2.99 in)
Cable end sleeve
Width of the device in
(not insulated)
1 HP (1 HP = 18 mm)
1 HP (1 HP = 18 mm)
horizontal pitches (HP)
Cable end sleeve
Installation position
discretionary
discretionary
(insulated)
Mounting/assembly -
· TS 35/7.5 according to EN 60715
· TS 35/7.5 according to EN 60715
Tightening torque
· TS 35/10
suitable DIN rails -
· TS 35/10
Stripping length
· TS 35/15 x 1.5
35 mm (1.38 in)
· TS 35/15 x 1.5
IP20
Protection class
IP20
-10 °C (14 °F) .. +55 °C (131 °F)
Operating temperature
-10 °C (14 °F) .. +55 °C (131 °F)
Detailed information and technical data on the
Impact resistance
IK07 according to IEC 62262
IK07 according to IEC 62262
module can be found in the user manual at
www.janitza.com (download area).
Transport and storage
Technical data on the basic device and information
The following information applies to devices which are
on how to proceed in the event of a fault can be
transported and stored in the original packaging
found in the usage information of your basic device.
1 m (39.37 in)
Free fall
1 m (39.37 in)
K55
K55
Temperature
-25 °C (-13 °F) up to +70 °C (158 °F)
-25 °C (-13 °F) up to +70 °C (158 °F)
5 to 95% at 25 °C (77 °F)
5 to 95% at 25 °C (77 °F)
Relative humidity
without condensation
without condensation
Ambient conditions during operation, see basic device
Interface
· Via bus connector to series of devices
JanBus (proprietary)
· Via bus connector to series of devices
and modules.
and modules.
· Via shield terminals between the
· Via shield terminals between the
transfer modules with twisted pair,
transfer modules with twisted pair,
shielded data cable (line connection
shielded data cable (line connection
1:1), e.g.:
1:1), e.g.:
Lapp Unitronic LiYcY (TP) 4x2x0.5
Lapp Unitronic LiYcY (TP) 4x2x0.5
· The maximum bus length of the
· The maximum bus length of the
JanBus is 100 m.
JanBus is 100 m.
5. Check the fit of your device and module series
and mount end brackets.
6. Finally, wire your series of measurement devices
and modules, observing the usage information
for all integrated devices and modules.
7. Apply voltage to the basic device (system). The
basic device detects the modules automatically.
2. transfer module 800-CON (with
2. transfer module 800-CON (with
input bus connector) in the remote
input bus connector) in the remote
measuring point with further modules
measuring point with further modules
End bracket
End bracket
End bracket
DIN rail
Terminal connection capacity
Connectable conductors.
Only one conductor can be connected per terminal.
Single core, multi-core,
0.2 - 1.5 mm
, AWG 24-16
0.2 - 1.5 mm
2
, AWG 24-16
2
fine-stranded
Cable end sleeve
0.2 - 1.5 mm
2
, AWG 26-16
0.2 - 1.5 mm
2
, AWG 26-16
(not insulated)
Cable end sleeve
0.2 - 1 mm
, AWG 26-18
0.2 - 1 mm
2
2
, AWG 26-18
(insulated)
0.2 - 0.25 Nm (1.77 - 2.21 lbf in)
Tightening torque
0.2 - 0.25 Nm (1.77 - 2.21 lbf in)
7 mm (0.2756 in)
Stripping length
7 mm (0.2756 in)
INFORMATION
INFORMATION
Detailed information and technical data on the
module can be found in the user manual at
www.janitza.com (download area).
Technical data on the basic device and information
on how to proceed in the event of a fault can be
found in the usage information of your basic device.
9