Fiberoptic fip-repeater

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4 LED Indicators
4 LED Indicators
OZD FIP G3
System
Port 1
Port 2
Port 3
Fig. 13: LED indicators on front panel
OZD FIP G3 ...
Version 3.2 08/07
All manuals and user guides at all-guides.com
Port 1
System
Green:
Repeater in operation, data traffic occurring
Red:
– No data received at Port 2 and/or Port 3
(e.g. cable breakage)
– not data received at Port 1 after impressing
the operating voltage resp. after a failure
(the device checks once for data receiving
at Port 1 after impressing the operating
voltage resp. after failure)
– No data traffic at any port for over 500 ms
– Short circuit at the electrical port
Not lit:
– No voltage supply
– Internal device fault
Port 1 (electrical)
Green:
Input signal applied
Orange: – No input signal at any port for over 500 ms
– Short circuit at the electrical port
(System LED then also red)
Not lit:
Currently no input signal at this port
Port 2 (optical)
Green:
Input signal applied
Orange: No input signal at any port for over 500 ms
Not lit:
Currently no input signal at this port
Port 3 (optical)
Green:
Input signal applied
Orange: No input signal at any port for over 500 ms
Not lit:
Currently no input signal at this port