The AS-i communication (yellow cable) must be switched off during
the infrared addressing. To do so, disconnect the master.
Supply the slaves with voltage via the AS-i power supply. Addressing is
carried out via the IR addressing cable E70211.
When the ifm AS-i power supplies SL are used the communication can
be deactivated via a plug on the power supply.
If a slave with the ID code "A" (option of extended addressing mode)
is connected to a master of the first generation (version 2.0), the para-
meter P3 must be 1 and the output bit D3 = 0*. The output bit D3
must not be used.
If a slave with the ID code "A" (option of extended addressing mode)
is connected to a master of the first generation (version 2.0), an
address between 1A and 31A must be assigned to this slave.
Operation
Check the safe functioning of the unit. Display by LEDs:
• LED 1 yellow:
• LED green:
• LED 2 red is lit:
• LED 2 red flashing:
• LED 3:
Overload and short circuit of the input supply are signalled to the AS-i
master (version 2.1) via the "peripheral fault" flag in the status register.
input switched
voltage supply o.k.
AS-i communication error, slave does not
participate in the "normal" data exchange,
e. g. slave address 0
peripheral fault, e.g. overload or short cir-
cuit of the sensor supply
infrared reciever
* default setting