Tab. 16: LCP DX Supervisor-Tabelle – Digitale Variablen
BMS Ad-
Description
dress
1
Digital input 1: Remote Condenser Alarm
(optional)
2
Digital input 2: Drive/Compressor Overload
3
Digital input 3: High Pressure Switch
4
Digital input 4: Low Pressure Switch (optio-
nal)
5-6
Reserved - (not used or other special appli-
cation or internal debug)
7
Digital input 7: Fans Overload Alarm
8
Digital input 8: Pump Overload Alarm
9
Digital input 9: Filter Clogged Alarm (optio-
nal)
10
Digital input 10: Remote ON/OFF
7
11
General Inverter Alarm
12
Power+ Drive Off-Line Alarm
13
Mode Regulation (0=RACK/ROW; 1=
ROOM)
14
Digital output 13: Pre/Post Heater 3 On (op-
tional)
15-16
Reserved - (not used or other special appli-
cation or internal debug)
17
Digital output 1: General alarm Contact
18-21
Reserved - (not used or other special appli-
cation or internal debug)
22
Digital output 6: FreeCooling Pump On (op-
tional)
23-26
Reserved - (not used or other special appli-
cation or internal debug)
27
Digital output 11: Pre/Post Heater 1 On (op-
tional)
28
Digital output 12: Pre/Post Heater 2 On (op-
tional)
29
Command to reset all alarms by Supervisor
30
Envelope Alarm: Memory alarm compressor
forced off working out envelope
31
Compressor startup failure alarm: reach max
retry number
32
Compressor startup failure alarm used for
the alarm mask visualization
44
UOM
Min
Max
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
---
0
1
Read/
Note
Write
R
Customer
R
Customer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
only for Service/
Manufacturer
R
Customer
R
Customer
R/W
only for Service/
Manufacturer
R
only for Service/
Manufacturer
R
only for Service/
Manufacturer
R
only for Service/
Manufacturer
Rittal Liquid Cooling Package