3. Operation
Mains connection:
400 V / 50 Hz / 16 A CEE
Starting up:
1. CEE-plug into the suitable socket. (neutral required)
2. function choice (heating or cold-ventilation)
1
2
Switch 1 (heating)
0 = off
1 = cold-ventilation
2 = 4500 W
3 = 9000 W
When the switch 1 is connected to a heating mode, the heater will automatically shut off when reaching
the set temperature (switch 2).
The fan continues operating for better air circulation.
After shutting off, the fan will continue
until no more residual heat is present (after-cooling function).
When the switch 1 is set to ventilation, only the fan motor is in operation.
Switch 2 (temperature thermostat)
In the heating operating mode, the room temperature can be controlled between 5° and 40°C.
Switching off
After switching off, wait until the fan switches off. Only then may the plug be pulled out.
Abnormal temperature protection:
If the unit overheats (this can happen due to a reduction in the air volume or due
to excessively high ambient temperatures), the safety temperature limiter (STB)
is triggered. This can be reset after the heaters have cooled down at switch A.
ATTENTION: As the heating elements are coated with a protective oil film during
production, a slight smoke is produced for a short time when the unit is switched
on for the first time. This smoke is normal and not dangerous to health.