9. Error indication
Error nr
Description
1
battery temperature too
high
2
battery voltage too high
3, 4, 5
temp. sense error
6, 7, 8, 9
voltage sense error
17
charger temperature too
high
18
Internal error
20
charger bulk time expired
34
Internal error
37
No input voltage (only for
the three output version)
65
charger disappeared
during operation
66
Incompatible device
67
BMS connection lost
113, 114
Internal error
115
116, 117,
Internal error
118
119
Settings invalid
Possible cause
Overcharging or fast charging
Wiring mistake, or another charger is
over charging
Wiring mistake or temperature sensor
broken
Wiring mistake
The heat generated by the charger
cannot be removed
After 10 hours of bulk charging, the
battery voltage has still not reached the
absorption voltage
Mains removed or ac-input fuse blown
One of the other chargers with which
this charger was synchronizing has
disappeared during operation
The charger is being paralleled to
another charger that has different
settings and/or a different charge
algorithm
Connection to the BMS lost.
Communication error
Solution
Check air flow near the battery
Improve cooling of environment.
The charger stops automatically and will
resume once the battery has cooled
down.
Check all charging equipment.
Check cables and connections.
Check the temperature sensor wiring
and if that doesn't help replace the
temperature sensor.
Check the voltage sensor wiring.
Check air flow of the cabinet
Improve cooling of environment
The charger stops automatically and will
resume once the charger has cooled
down.
Contact Victron service.
Possible cell failure or higher charge
current needed.
Contact Victron service.
Check mains availability and fuse.
To clear the error, switch the charger off
and back on.
Make sure all settings are the same and
update firmware on all chargers to the
latest version.
Check the VE.Can bus cabling. When
the charger needs to operate in stand-
alone mode again, go to the setup
menu #31 (BMS Present) and set to N.
Contact Victron service.
Check wiring and terminators.
Contact Victron service.
Restore defaults in the setup menu #62.