Cosmo CSUS50STG Montage- Und Betriebsanleitung Seite 79

Solar-übergabestation - 50 m

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

S O L A R T R A N S F E R S T A T I O N - 5 0 m
2
Storage tank 2
ΔTon
5.0 K
ΔToff
3.0 K
ΔTnom
6.0 K
Stnom
60 °C
Stmax
60 °C
Priority
2
HysSt
2.0 K
Rise
1.0 K
tMin
30 s
Min speed
30 %
Storage tank
Activated
Charging logic
Oscillating
charging
Type
succ. Charg-
ing
Oscilcharg
2 min
Circ.
15 min
Break speed
Pump speed
30 %
Pump delay
Delay
30 s
S O L A R / E L E C T I V E F U N C T I O N S / E X T. H E
Factory
Designation
setting
Ext. HE
Output
R4, B
Storage tank
1, 2
Sensor HE
S5
Target
temperature
ΔTon
5.0 K
ΔToff
3.0 K
Overrun
2 min
The switch-on temperature difference for
charging the storage tank 2 is set here.
The switch-off temperature difference for
charging the storage tank 2 is set here.
The nominal temperature difference for
charging the storage tank 2 is set here.
The storage tank nominal temperature of
storage tank 2 is set here.
The maximum temperature of the storage
tank 2 is set here.
f. ex. 85 °C
In case of over 60 °C in a storage tank with
service water a scalding protection has to be
provided!
The order of charging the storage tanks is set
here.
The hysteresis for the setting of the storage
tank charging is changed here.
The rise of revolution speed of the solar circuit
pump referred to ΔT is set here.
The minimal runtime of the solar circuit pump
during the charging process is set here.
The minimal speed of the solar circuit pump for
charging the storage tank is set here.
The charging of the storage tank can temporari-
ly be deactivated here.
Change to
The output for the secondary pump in the trans-
fer station is assigned here.
The solar charging of individual storage tanks
can be restricted here via the transfer station.
The sensor for the transfer station on the prima-
ry side before the heat exchanger is assigned
here.
A target temperature control can be activated
here.
Switch-on temperature difference for the
secondary pump of the transfer station
Switch-off temperature difference for the
secondary pump of the transfer station
Overrun time of the secondary pump of the
transfer station for use of residual heat.
7 9
Note