Commissioning Instructions
Positioner TZIDC-110 for PROFIBUS PA
Commissioning procedure
Always observe all safety instructions and
!
precautions in the operating instructions.
1. Turn on the air supply to the positioner.
2. Connect the bus with arbitrary polarity (or auxiliary power
9 V DC ... 32 V DC) to the bus terminals.
¬
C
%
mA
is displayed
conf
If the emergency shutdown module is installed, the supply vol-
tage for this module needs to be 24 V DC (terminals +85 / -86)
and the switch needs to be in its center position. Otherwise,
the device has no pneumatic function.
3. Check for proper mounting:
M
-
Press and hold
ODE
Wait until the countdown has run down from 3 to 0, then
M
release
and
ODE
(mode 1.x) is reached and indicated.
-
Press and hold
MODE
until mode 1.3 (manual adjustment within the sensor
range) is displayed. Release
-
Press
or
to move the actuator to its mechanical limit
stops in both directions, and note the values.
Recommended range:
between -28° and +28° for linear actuators
between -57° and +57° for rotary actuators
Minimum angle: 25°
Important:
The positioner should be mounted/adjusted such that the
portions of the sensor's operating range above and below
the center point are nearly identical. Use the rotation angle
of the position sensor in the positioner to its utmost extent.
4. Return to the remote level.
-
Press and hold
MODE
down has run down from 3 to 0.
-
Release
and
MODE
¬
C
%
mA
is displayed.
conf
5. Run the standard Autoadjust function.
-
Make sure that the remote level is activated.
linear
For a
actuator:
-
Press and hold
MODE
from 5 to 0, then release
-
Press and hold
MODE
run down from 3 to 0, then release
Standard autoadjustment is started automatically, and the
progress is displayed.
rotary
For a
actuator:
-
Press and hold
ENTER
¬
C
%
-
is displayed
mA
conf
-
Wait until the display has changed to
¬
C
%
mA
conf
-
Release
.
ENTER
-
Press and hold
ENTER
run down from 3 to 0, then release
Standard autoadjustment is started automatically, and the
progress is displayed.
When standard autoadjustment has completed successfully,
the determined parameters are saved automatically, and the
remote level is activated again.
If, however, an error should occur during standard autoadjust-
ment, error code 255 is briefly indicated.
ABB Automation Products GmbH
Schillerstr. 72 · 32425 Minden, Germany
Tel: +49 551 905-534 · Fax: +49 551 905-555
CCC-support.deapr@de.abb.com
E
and
NTER
simultaneously.
E
. The operating level
NTER
. Additionally briefly press
.
MODE
and
until the count-
ENTER
.
ENTER
until the countdown has run down
.
MODE
again until the countdown has
.
MODE
again until the countdown has
.
ENTER
The device then automatically changes over to parameter P1.1
Autoadjust at the configuration level. In this case:
- Press and hold
MODE
ral times until P1.6 "EXIT" is displayed.
- Release
. CANCEL is displayed. If not, briefly press
MODE
or
.
- Press and hold
ENTER
3 to 0.
The positioner automatically returns to the operating level. Briefly
press
twice to reach operating mode 1.3 "Manual adjustment
within the sensor range" and then check the positioner-actuator
assembly for proper mounting. Re-adjust if required (see operating
instructions for details) and then start standard autoadjustment
again.
Operating modes
Prodecure for mode selection from operating level:
Press and hold
MODE
as required. The selected operating mode is indicated.
Release
MODE
or rotation angle
Overview:
or
Mode
1.1 Positioning with fixed
setpoint; setpoint adjust-
ment via
or
.
1.2 Manual adjustment *
within the operating range.
Press
or
to adjust. **
1.3 Manual adjustment *
within the sensor range.
Press
or
to adjust. **
*) Positioning is not active.
**)For quick motion: press
Setting the bus address
From remote level: Change over to the operating level. Press
and hold
MODE
countdown has run down from 3 to 0. Release
.
ENTER
Switch to the configuration level: Press and hold
simultaneously. Additionally, briefly press
Keep
and
pressed until the countdown from 3 to 0 is fin-
ished (approx. 3 seconds). Do not release earlier.
"STANDARD" is displayed.
Set the bus address: Press and hold
briefly press
M
Release
ODE
setting). Press
address.
Save the bus address: Press and hold
countdown has run down from 3 to 0. Release
press and hold
MODE
required to call P1.6 "EXIT". Press
ter to NV_SAVE.
Return to the operating level: Press and hold
the countdown has run down from 3 to 0.
Return to remote level:
until the countdown has run down, then release.
ENTER
The company's policy is one of continuous product improvement and the right
is reserved to modify the information contained herein without notice.
41/18-74 XA
. Additionally, briefly press
until the countdown has run down from
. Additionally briefly press
. The position is indicated as a percentage
Mode display
Position display
¬
C
%
mA
conf
¬
C
%
mA
conf
¬
C
%
mA
conf
and
together.
and
simultaneously until the
ENTER
ENTER
MODE
or
until P1.5 "ADDRESS" is displayed.
. "126, ADDRESS" is displayed (factory
or
to increment or decrement this bus
ENTER
. Additionally press
or
or
to set this parame-
Press and hold
Printed in the Fed. Rep. of Germany (02.2009)
or
seve-
as often
¬
C
%
mA
conf
¬
C
%
mA
conf
¬
C
%
mA
conf
and
MODE
and
once.
P1._
. Additionally
until the
. Then
ENTER
as often as
until
ENTER
and
MODE
© ABB 2009