7. Commissioning
Before commissioning the device, check that it has been properly installed, and
make sure that it does not show any visible defects.
The device may by commissioned only by appropriately qualified and trained
personnel who have read and understood the user manual.
The device may only be operated within its specifications! (Compare the technical
data in the data sheet)
The instantaneously present output signal can be checked without breaking the current
loop by using a mA ammeter. This is done by connecting a mA ammeter to the "TEST"
and "-" electrical connector terminals and measuring the output signal present.