Herunterladen Inhalt Inhalt Diese Seite drucken

Preparing To Install The System Cover/System Seal; Fhrk-Quality Seal - Hauff-Technik HSI90 Montageanleitung

Vorschau ausblenden Andere Handbücher für HSI90:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Slanted wall insert
HSI90/HSI150
8 Preparing to install the system cover/sys-
tem seal
Observe before mounting the system cover:
• Complete removal of sealing pack sticker (pro-
tective film) prior to system cover installation
(see Fig.: 12)!
• Carefully open the blind cover! Water pressure
possible inside the cable entry!
• Do not open the blind cover of the wall insert
until just before installing the cable. Observe
theinstallation instructions for the system co-
ver
• Any cable entries that are not required may be
used as pressure-tight back-up entries if there
isan undamaged Hauff quality seal on the clos-
ing cover.
• Do not knock the blind cover in with a ham-
mer or sharp object!
• Open cable entries, which are to be used as
back-up entries, or closing cover which have-
been opened accidentally, should be fitted
with new HSI150 DT/DTS respectively HSI90 D
blind covers!
• Do not reuse uninstalled or damaged closing
covers!
1
Remove protective foil from the wall insert completely
(after warming slightly).
2
If necessary, clean out concrete residue from the
wrench threads on the black blind cover.
Use the SLS 6G(D) flexible socket wrench to open the
blind cover via the wrench threads by twisting to the
left (see Fig.: 13).
Further information on installing system co-
vers/system seals, see respective installation in-
structions.

9 FHRK-Quality Seal

Tested products
Test report numbers
FHRK-Testing Specification
Service telephone + 49 7322 1333-0
HSI150 1xZ K S_°/X,
HSI150 1xZ K2 S_°/X
G 30 322-3-10
21DE-01298
KD 101
Subject to change!
Art. Nr.: 5090020175 Rev.: 03/2023-07-14