9. Technical data
Type/ Nominal voltage range: DSP-UB 1:
10 ... 1100 V AC
10 ... 1500 V DC
Nominal frequency range: DC/15 ... 500 Hz
Measurement range:
10 ... 1100 V AC
10 ... 1500 V DC
± 2 % + 5 D
Input resistance:
448 kΩ at 1500 V
Current peak value I
:
< 3,4 mA
s
On-time:
at max nominal voltage
TR on 120 s
RT off max 240 s (recovery time)
Display :
2 red LEDs for voltage
2 green LEDs for no voltage
LCD 1999 Digit
two-color backlight
Polarity:
LCD voltage type - / ~
integrated self-test:
connection cable, extension,
electronic, display,
protective resistors
Power supply:
9 V-Block IEC 6LR61 / 6LF22 /
6LP3146 alkali-manganese
Overvoltage category: CAT IV 600 V / CAT III 1000 V
Surge voltage strength: >12 kV (1,2/50 µs)
Test voltage:
6 kV
Operating temperatures:
Casing:
ABS, display cover made of
impact resistant polycarbonate
Design:
two-pole voltage tester with
a screwed-on 850 mm extension
made of GRP with O-electrode
for testing covered busbars,
PUR sheathed cable - double
insulated with contact magnet
for connection to the grounded
running rail
Protection category:
IP 65,
Device can be used during
precipitation
Connecting line:
PUR sheathed cable,
1500 V, 1,5 m with firmly
attached magnet
Standards:
voltagte indication and LEDs
in accordance with
IEC 61243-2
design to
IEC 61243-3 / 61243-2
EMV requirements:
DIN-EN 61326
Dimensions/Weigth:
1150 x 70 x 70 mm
450 g
22
-15 ... + 55°C