4 User interface
4.5.2

About types of malfunctions

When a malfunction is detected:
▪ The error code (c) is shown on the display, alternating with the
main value (b). This allows immediate identification of the
malfunction.
▪ The "service" icon (a) is shown on the display.
a
b
There are 2 types of malfunctions:
▪ Warning
▪ The buzzer does not sound.
▪ No relay is activated.
Errors belonging to this category include defrost ended after
maximum time, dirty condenser, HACCP alarms and configuration
errors.
▪ Alarm
▪ The buzzer sounds.
▪ The concerning relay is activated.
This category includes alarms for which with the relay is
configured as an alarm, probe errors, temperature alarms, frost
protection, communication errors with the VCC compressor,
power supply over and under voltage, etc.
INFORMATION
If there is an active alarm the buzzer will sound. Press any
button to mute the buzzer.
Take into account that:
Alarms and warnings are identified by error codes. For the error
code table, see "8 Troubleshooting" [ 4  17].
If more than one warning/alarm occurs, they are displayed in
sequence.
Digital outputs can be configured to signal the warning/alarm status,
normally open or normally closed.
A warning/alarm can also be activated from an external contact,
immediate or delayed.
The warning and alarm signals can be immediate or delayed by
parameter.
4.5.3

To reset an alarm or warning

Both warnings and alarms can be reset automatically, manually, or
semi-automatically (see alarm table):
▪ Automatic: when the cause is no longer present, the alarm also
ceases.
▪ Semi-automatic: reset is automatic three times in an hour, after
which a manual reset is required.
▪ Manual: when the cause is no longer present, the alarm remains
active until manually reset by parameter.
The alarms can be reset manually using parameter rSA , via the
user terminal or configuration tool, or in Daikin User (Bluetooth
connection only) using the specific command on the alarms page
("Service" or "Manufacturer" level access is required).
If the condition that generated the alarm is still present, the alarm
is reactivated after resetting.
Operation manual
14
4.5.4
Alarm log
When an alarm is cleared, it is stored in the alarm log containing a
maximum of 5 alarms, in a FIFO list (the 6th alarm overwrites the
first alarm, and so on). The error log is accessible via the user
terminal, via supervisor or the Daikin User app (Bluetooth connection
only).
a
c
The controller can record both periodic and event logs, which can
then be viewed and downloaded using the Daikin User app and
commissioning tools.
1 To view the periodic logs in Daikin User: Select Service Area →
Trend -> (tab) Logs.
2 To view the event logs in Daikin User: Select Service Area ->
Trend → (tab) Events.
a
The log view is pre-set, however it can be changed using the editing
tools (c). In addition, the pre-set views loaded on the device allow
the main values to be filtered (temperature, HACCP alarms,
blackouts, etc.). To download the logs, use the drop-down menu at
the top right.
The periodic logs record the main values at regular intervals, as
shown in the table below.
Control temperature
Current temperature set point.
Current humidity
Current humidity set point
Maximum temperature in the period
Minimum temperature in the period
Current evaporation temperature
Current condensing temperature
Compressor, minutes ON in the
period
Compressor, starts in the period
Evaporator fan, minutes ON in the
period

About the alarm log

b c
a
Preset
b
Periodically logged variables
c
Tools to modify the display
d
Alarm status (0: not active, 1: active)
e
Alarm code (see the alarms table)
Logged value
LMSEY1A09/13 + LMSEY2A19/25
d e
UOM
Period
°C/°F
5 min
°C/°F
1 h
% rh
1 h
% rh
1 h
°C/°F
1 h
°C/°F
1 h
°C/°F
1 h
°C/°F
1 h
min
1 h
-
1 h
min
1 h
Daikin LMS
4P728169-1B – 2023.07