Herunterladen Inhalt Inhalt Diese Seite drucken

Parameters - Daikin LMS Serie Betriebsanleitung

Vorschau ausblenden Andere Handbücher für LMS Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 20
4.3.3

Parameters

Name
/5
Unit of measure:
▪ 0: °C
▪ 1: °F
/6
Display decimal point:
▪ 0: Yes
▪ 1: No
/t1
Display on user terminal:
▪ 0: not configured
▪ 1: value of S1
▪ 2: value of S2
▪ 3: value of S3
▪ 4: value of S4
▪ 5: value of S1H
▪ 6 to 8: not available
▪ 9: control probe
▪ 10: virtual probe
▪ 11 to 14: not available
▪ 15: current control setpoint
/t2
Display on remote display:
▪ 0 to 15, see /t1 (above)
Ad
Delay time for high and low temp. alarms (AH, AL)
Add
High temp. alarm bypass time for door open
AH
Relative high temperature alarm threshold
AL
Relative low temperature alarm threshold
Eco
Eco mode status:
▪ 0 OFF
▪ 1 ON
Fr
SW version of the controller (read only)
H11
BMS serial port configuration (stop bits and parity):
▪ 0: 1 stop bit, no parity
▪ 1: 2 stop bits, no parity
▪ 2: 1 stop bit, even parity
▪ 3: 2 stop bits, even parity
▪ 4: 1 stop bit, odd parity
▪ 5: 2 stop bits, odd parity
HAn
Number of type HA alarms (read-only)
Hb
Buzzer:
▪ 0: disabled
▪ 1: enabled
HFn
Number of type HF alarms (read-only)
HU
Humidity level: 0: low; 1: medium; 2: high
rd
Temperature control differential
rSA
Reset alarms
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728169-1B – 2023.07
Description
4 User interface
Default
Min.
Max.
0
0
1
0
0
1
9
0
15
0
0
15
120
0
240
5
1
240
0
0
555/
∆ °C/°F
999
0
0
200/
∆ °C/°F
360
1
0
1
r.04
0
0
0
0
6
1
0
1
0
0
6
1
0
2
2/
0.1/
99.9/
∆°C/°F
3.6
0.2
179.2
0
0
1
(a)
UoM
Menu
Pro
Pro
Pro
Pro
min
ALM
min
ALM
ALM
ALM
dir
dir
CnF
PSd
CnF
PSd
PSd
CtL
ALM
Operation manual
11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis