5.4.3 Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP
switches of a new product are set to 'off').
DS-1 3 position switch
off
DS-2 Charge voltage
off
DS-3 Charge voltage
off
DS-4 Frequency
off
DS-5 Search mode
off
DS-6 Store setting
Example 1: (factory setting)
1
No 3 position
switch connected
2, 3
GEL 14.4 V
4
Frequency: 50Hz
5
Search mode off
6 Store setting: off→ on→ off
Store the settings by changing switch ds-6 from off to on, and then back to off.
The LEDs 'charger' and 'alarm' will flash to indicate acceptance of the settings.
6. MAINTENANCE
The MultiPlus does not require specific maintenance. It will suffice to check all connections
once a year. Avoid moisture and oil/soot/vapours, and keep the device clean.
18
All manuals and user guides at all-guides.com
DS-1
off
DS-2
on
DS-3
off
DS-4
off
DS-5
off
DS-6
Example 2
1
No 3 position
switch connected
2,3
AGM 14,7V
4
Frequency: 50Hz
5
Search mode off
6 Store setting: off→ on→ off
DS-1
on
DS-2
on
DS-3
on
DS-4
on
DS-5
on
DS-6
Example 3
1
3 position
switch connected
2, 3
Tubular plate 15V
4
Frequency: 60Hz
5
Search mode on
6 Store setting: off→ on→ off