Rooms with straight ceilings
(slope angle < 20°)
1/2
0,5
Fig. 11
Rooms with straight ceilings
Allowed
Not allowed
Note the following for locations in rooms
with straight ceilings:
f Select the highest mounting point on
the ceilings.
f Mount the devices horizontally to
the mounting surface.
54
1/2
0,5
0,5
Operating Manual: FRWM200 - Smoke Alarm Device with Radio Link
Narrow spaces or corri-
dors (1-3 m wide)
In addition, observe the following for lo-
cations in narrow rooms or corridors that
are 1-3 m wide:
f Keep the distance of less than 7.5 m
between the front surface (end of
the corridor) and the first device.
f Keep the distance of less than 15 m
between two devices.
Narrow spaces or corridors (< 1 m wide)
In addition, observe the following for lo-
cations in narrow rooms or corridors that
are less than 1 m wide:
f Keep distance from surrounding walls
(exception: distance less than 0.5 m).
Narrow spaces or corridors
(floor space < 6 m
An exception are narrow rooms and cor-
ridors that have an area of less than 6 m
)
2
.
2