The use of smoke alarm devices is governed
by DIN 14676.
Minimum equipment
Minimum equipment
Bedrooms
•
Children's bedroom
•
Guest room
•
Hallways and all other rooms
•
which serve as an escape route
Stairwells of family houses
•
Optimal equipment
Optimal equipment
All living and hobby rooms (except in
•
Berlin and Brandenburg – here such
equipment is also required by law)
Heating and work spaces
•
Office or workroom
•
Cellar
•
Attic
•
Conditional equipment
Conditional equipment
In kitchens, smoke alarm devices must
•
only be installed when false alarms
(e.g., caused by steam) are excluded
Not recommended
Not recommended
Bathrooms are excluded from the
•
installation of smoke alarm devices
due to the high development of steam
EN
Operating Manual: FRWM200 – Smoke Alarm Device with Radio Link
4.1 Area to be monitored
Use a device if at least one of the following
applies:
Monitoring area less than 60 m
•
and ceiling height of less than 6 m
Ceiling panels (height lower
•
than 20 cm) with joists (ceiling
surface less than 36 m
Use additional equipment if at least one of the
following applies:
Monitoring area greater than 60 m
•
Ceiling height greater than 6 m
•
High partial walls
•
Separating pieces of furniture
•
Platform / gallery (area greater than
•
16 m², at least 2 m long and wide)
,
2
)
2
2
51