Air Temp
Air Temp Filtered
Air Temp Geometrical
Name
Air Temp BMS Override
8. Anhang
DHW CONTROLLERS
DHW Calefa
Aggregated warning
Aggregated error
Warning - Retentive Low Energy
Error - DHW temp high
Error - Motor failure
Error - DHI sensor failure (source inlet)
Error - DHO sensor failure (source return)
Error - DHW sensor failure
Error - DCW sensor failure
Warning - Pressure high
Warning - Pressure low
Error - Pressure critical low
Desired DHW temp
State
Blocking source
Circulation state
Measured DHW temp
Source - Inlet temp
Source - Return temp
Pressure
Name
Mode
User interface access level
(calefa display lock)
Block request
Power consumption limit
DHW temp set
DHW bypass temp
Circulation - Pump present
Circulation - Inlet temp
Exclude from vacation
Exclude from standby
ITC CONTROLLERS
ITC1
Aggregated warning
Aggregated error
Error - Inlet Sensor Failure
Error - Servo Failure
Error - Return Sensor Failure
Error - Outdoor Sensor Failure
Error - High temp cut-off activated
Error - Frost protection activated
State
Blocking source
Pump - Demand
Pump - State
Measured inlet temperature
Desired inlet temperature
Measured return temperature
Main supplier temperature
Name
Regulator - P value
Regulator - I value
Regulator - Hysteresis
Heat curve - type
Heat curve - manual slope
Heat curve - parallel displacement
Heat curve - min inlet
Heat curve - max inlet
Heat curve - gain
Return temp limiter -function
Return temp max limiter - Limit
Return temp max limiter - Gain
Return temp max limiter - Priority over inlet
Return temp min limiter - Limit
Return temp min limiter - Gain
Optimization - boost
Optimization - boost percent
Optimization - ramping
Optimization - ramping time
Frost protection - Mode
Frost protection - Temp
High Temp Cut-Off - Mode
High Temp Cut-Off - Temp
Cooling Regulator - P value
Cooling Regulator - I value
Cooling Regulator - Hysteresis
Cooling inlet temp min
Cooling inlet temp max
ITC2
Same as ITC1
HCC CONTROLLERS
HCC1
Aggregated warning
Aggregated error
Error - inlet sensor failure
Error - High temp cut-off activated
State
150
Sentio Technisches Handbuch
R
Input Register
03301
val_d2_fp100
Used for Frost protection, Cooling blocking, H/C mode switching
R
Input Register
03302
val_d2_fp100
Used in Heat curve calculations, H/C blocking (to be changed)
R
Input Register
03303
val_d2_fp100
Not yet used in the code (pending issue)
R/W Holding Register
03301-03316
val_utf8
String description (32 Bytes, UTF8, NULL terminated)
R/W Holding Register
3317
val_d2_fp100
Enables to put artificial externa temperature used for ITC1
INVALID ... it will not be used
065xx
R
Discrete Inputs
06501
A problem is pending in DHW
R
Discrete Inputs
06502
A critical problem is pending in DHW
R
Discrete Inputs
06503
R
Discrete Inputs
06504
R
Discrete Inputs
06505
R
Discrete Inputs
06506
R
Discrete Inputs
06507
06508
R
Discrete Inputs
R
Discrete Inputs
06509
R
Discrete Inputs
06510
R
Discrete Inputs
06511
R
Discrete Inputs
06512
R
Input Register
06501
val_d2_fp100
Shows the desired temperature of the domestic hot water.
R
Input Register
06502
val_u1
1 IDLE
2 HEATING (hot water is consumed by user)
3 BYPASS (keeping heat exchanger hot for circulation)
4 BLOCKED_HEATING
5 BLOCKED_BYPASS
Shows, whether the system wants to heat or to have bypass activated.
R
Input Register
06503
val_u1
Same as Heating/Cooling blocking source
R
Input Register
06504
val_u1
0 NONE (disabled)
1 IDLE
2 ON
R
Input Register
06505
val_d2_fp100
Current temperature of the domestic hot water flowing from DHW
R
Input Register
06506
val_d2_fp100
Current temperature of the water incoming from the heat source.
R
Input Register
06507
val_d2_fp100
Current temperature of the water returning to the heat source.
R
Input Register
06508
val_d2_fp100
Current pressure of the secondary system
R/W Holding Register
06501 - 06516
val_utf8
String description (32 Bytes, UTF8, NULL terminated)
R/W Holding Register
06517
val_u1
0 SCHEDULE
1 SCHEDULE_ADAPTIVE
2 ECO
3 COMFORT
Eco = circulation and hot bypass are disabled
Comfort = circulation and hot bypass are enabled
R/W Holding Register
06518
val_u1
< 40 USER (user menu)
>= 40 INSTALLER (inst. menu)
R/W Holding Register
06519
val_u1
0 NONE
1 BLOCK_REQUEST
When BLOCK_REQUEST is set, then the system blocks heating and bypass to eliminate
consumption from heat supplier.
R/W Holding Register
06520
val_u2
R/W Holding Register
06521
val_d2_fp100
Requested temperature of domestic hot water.
R/W Holding Register
06522
val_d2_fp100
R/W Holding Register
06523
val_u1
0 DISABLED
1 ENABLED (scheduler)
R/W Holding Register
06524
val_d2_fp100
When circulation is enabled and there is NO dhw consumption, then the DHW
temperature is regulated to this value.
R/W Holding Register
06525
val_u1
Do not allow the Vacation mode
R/W Holding Register
06526
val_u1
Do not allow the Standby mode
073xx
R
Discrete Inputs
07301
A problem is pending in ITC
R
Discrete Inputs
07302
A critical problem is pending in ITC
07303
R
Discrete Inputs
Missing or broken sensor
R
Discrete Inputs
07304
Missing or broken servo
R
Discrete Inputs
07305
Missing or broken sensor
R
Discrete Inputs
07306
Missing or broken sensor
07307
R
Discrete Inputs
Safety mechanism "high temp cut-off" is activated
R
Discrete Inputs
07308
Safety mechanism "frost protection" is activated
R
Input Register
07301
val_d1
1 IDLE
2 HEATING
3 COOLING
4 BLOCKED_HEATING
5 BLOCKED_COOLING
R
Input Register
07302
val_u1
Same as Heating/Cooling blocking source
07303
R
Input Register
val_u1
1 IDLE
2 ON
R
Input Register
07304
val_u1
1 IDLE
2 ON
R
Input Register
07305
val_d2_fp100
Measured temperature of the inlet heating/cooling water.
R
Input Register
07306
val_d2_fp100
Desired temperature of the inlet heating/cooling water.
The value which the ITC regulator wants to meet.
R
Input Register
07307
val_d2_fp100
Measured return temperature
R
Input Register
07308
val_d2_fp100
Main supplier temperature
R/W Holding Register
7301-7316
val_utf8
String description (32 Bytes, UTF8, NULL terminated)
R/W Holding Register
07317
val_d2_fp10
Proportional gain of temperature regulator
R/W Holding Register
07318
val_u2
Integrating time of temperature regulator
R/W Holding Register
07319
val_d2_fp100
Hysteresis
R/W Holding Register
07320
val_u1
0 MANUAL
1 CALCULATED
2 UNDERFLOOR
3 RADIATORS
R/W Holding Register
07321
val_d2_fp10
Curve slope.Used only in MANUAL
R/W Holding Register
07322
val_d2_fp100
Shifts calculated temperature up/down
07323
R/W Holding Register
val_d2_fp100
Lowest possible temperature
R/W Holding Register
07324
val_d2_fp100
Highest possible temperature
R/W Holding Register
07325
val_d2_fp10
Static gain of desired temperature calculation
R/W Holding Register
07326
val_u1
0 OFF
1 MIN
2 MAX
07327
R/W Holding Register
val_d2_fp100
Maximum allowed return temperature (limits inlet temperature)
R/W Holding Register
07328
val_d2_fp10
Return limiter proportional gain.
Use high value fast acting system, low value for slow acting system.
R/W Holding Register
07329
val_u1
0 NO_PRIORITY
1 PRIORITY (return limiter can override "Heat curve - min inlet")
R/W Holding Register
07330
val_d2_fp100
Minimal allowed return temperature (limits inlet temperature)
07331
R/W Holding Register
val_d2_fp10
Return limiter proportional gain.
Use high value fast acting system, low value for slow acting system.
R/W Holding Register
07332
val_u1
Boost desired temperature by "Optimization - boost percent" for 1 hour
0 DISABLED
1 ENABLED
R/W Holding Register
07333
val_u1
Boost percent
R/W Holding Register
07334
val_u1
Rise desired temperature over ramping time.
0 DISABLED
1 ENABLED
R/W Holding Register
07335
val_u1
Ramping time
R/W Holding Register
07336
val_u1
Activate heating in assigned loops whe inlet temperature drops
bellow "Frost protection - Temp"
R/W Holding Register
07337
val_d2_fp100
Frost protection limit
07338
R/W Holding Register
val_u1
Heating is blocked, when inlet temperature exceeds the limit.
Alarm is raised, pump is switched off (ignoring all pump delay).
0 DISABLED
1 ENABLED
R/W Holding Register
07339
val_d2_fp100
Limit temperature for High Temp Cut-Off
R/W Holding Register
07340
val_d2_fp10
Proportional gain of temperature regulator in cooling mode
R/W Holding Register
07341
val_u2
Integrating time of temperature regulator in cooling mode
R/W Holding Register
07342
val_d2_fp100
Hysteresis in cooling mode
R/W Holding Register
07343
val_d2_fp100
Lowest possible temperature in cooling mode
R/W Holding Register
07344
val_d2_fp100
Highest possible temperature in cooling mode
074xx
077xx
R
Discrete Inputs
07701
A problem is pending in ITC
R
Discrete Inputs
07702
A critical problem is pending in ITC
Discrete Inputs
07703
R
Discrete Inputs
07704
Safety mechanism "high temp cut-off" is activated
R
Input Register
07701
val_d1
1 IDLE
2 HEATING
3 COOLING
4 BLOCKED_HEATING
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
YES
YES
YES
YES
CHANGED
YES
YES
YES
YES
YES
YES
YES
CHANGED
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
FORMAT
YES
YES
YES
CHANGED
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
YES
-
YES
YES
-
YES
YES
YES
-
-
YES
YES
-
-
YES
YES
-
-
YES
YES
-
-
YES
YES
-
-
YES
YES
-
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
CHANGED
YES
YES