Anhang; Modbus Anhang; Parameter - wavin Sentio Technisches Handbuch

Regelsystem für fußbodenheizung und -kühlung
Vorschau ausblenden Andere Handbücher für Sentio:
Inhaltsverzeichnis

Werbung

8. Anhang

Modbus Anhang

Object

Parameter

LOCATION
Location
Aggregated warning
Aggregated error
Address space major version
Address space minor version
Dev type
Dev hw version
Dev sw version
Dev sw version minor
Dev serial number prefix
Dev serial number
Address space major version
Address space minor version
Modbus slave address
Modbus baudrate
Modbus mode
Modbus password
Modbus parity
Modbus stop bits
Location name
Standby
Vacation
Datetime
Daylight saving time allowed
Cooling minimum outdoor temperature
Heating maximum outdoor temperature
Update mode
Heating/Cooling mode BMS override
Timezone number
ROOMS (INDOOR ZONES)
Room 1
ROOM TYPE
NORMAL, DUMMY
Aggregated warning
NORMAL, DUMMY
Aggregated error
NORMAL
Warning - low battery
NORMAL
Error - peripheral lost
NORMAL, DUMMY
Desired temp
NORMAL, DUMMY
General Heating/Cooling state
(radiator | underfloor | integration)
NORMAL, DUMMY
General Heating/Cooling blocking source
(radiator | underfloor | integration)
NORMAL
Air temperature
NORMAL
Floor temperature
NORMAL
Relative humidity
NORMAL
Calculated dew point
NORMAL
Associated to Radiators
NORMAL
Associated to UFHC
NORMAL
Associated to Drying
(humidity control)
NORMAL
Associated to Thermal integration
(thermal. integ control)
NORMAL
Radiators state
(air temperature)
NORMAL
Underfloor Heating/Cooling state
(floor temperature)
148
Sentio Technisches Handbuch
NORMAL
Drying state
(relative humidity)
R/W Modbus Table
Modbus
Data type
Description
Address
000xx
This object contains values shared across all objects in the location.
R
Discrete Inputs
00001
A problem is pending in whole system (Location)
R
Discrete Inputs
00002
A critical problem is pending in whole system (Location)
R
Input Register
00001
val_u1
= 3 (Incremented on incompatible change)
R
Input Register
00002
val_u1
= 1 (Incremented on compatible change)
00010
R
Input Register
val_u1
1 - CCU-208
2 - DHW-201 (Calefa)
R
Input Register
00011
val_u1
R
Input Register
00012
val_u1
00013
R
Input Register
val_u1
R
Input Register
00014
val_u2
= 1530
R
Input Register
00015-00016
val_u4
00001
R/W Holding register
val_u1
= 3 (Incremented on incompatible change)
R/W Holding register
00002
val_u1
= 1 (Incremented on compatible change)
R/W Holding register
00003
val_u1
Allowed values: 1 to 247
Default: 1
R/W Holding register
00004
val_u2
Allowed values: 9600, 19200, 38400, 57600
Default:19200
R/W Holding register
00005
val_u1
0 DISABLED
1 READ_ONLY
2 READ_WRITE
3 WRITE_WITH_PASSWORD
Default: 0
W
Holding register
00006
val_u2
When Modbus mode = WRITE_WITH_PASSWORD, the write commands are disabled until
this register is written by a valid password.
Once the password is written, the the write comands are accepted for next 11 minutes.
Then the password has to be set again.
Two steps are required for password change:
1. Write the old password
2. Write the new password before 11 minutes elapses.
Default password: 1234, Write only, range for passwd is 1 - 65535
R/W Holding register
00007
val_u1
0 - NONE
1 - ODD
2 - EVEN
R/W Holding register
00008
val_u1
0 - 1 STOP BIT
1 - 2 STOP BITS
00010-00025
R/W Holding register
val_utf8
Placeholder for 32 bytes of location description.
See "working with strings" chapter for more info.
R/W Holding register
00026
val_u1
0 OFF
1 ON
R/W Holding register
00027
val_u1
0 OFF
1 ON
R/W Holding register
00028-00029
val_u4
Current time
- unit timestamp format
- localtime including DST (if enabled)
R/W Holding register
00030
val_u1
0 Disabled
1 Enabled
R/W Holding register
00031
val_d2_fp100
Cooling is blocked, when outdoor temperature is lower than this value.
R/W Holding register
00032
val_d2_fp100
Heating is blocked, when outdoor temperature is higher than this value.
R/W Holding register
00033
val_u1
0 Dont allow from mobile app
1 Enabled
2 Disabled entirely
R/W Holding register
00034
val_u1
Note: Only available in hardware profiles, which support manual H/C change-over. In other
profiles override is set to DISABLED.
0 - DISABLED
1 - HEATING MODE
2 - COOLING MODE
3 - H/C MODE SET BY EXTERNAL SWITCH (only when HW input is available)
R/W Holding register
00035
val_u2
For list of supported timezones see tab "Timezone list"
001xx
Note: Dummy room is special type of room, where no thermostat or sensor is installed.
Dummy room does not support cooling mode.
To find out room type, check input register 127.
R
Discrete Inputs
00101
A problem is pending in Room
R
Discrete Inputs
00102
A critical problem is pending in Room
R
Discrete Inputs
00103
There are one or more peripherals in the room with low battery.
R
Discrete Inputs
00104
There are one or more peripherals in the room which are not responding.
R
Input Register
00101
val_d2_fp100
Shows the desired temperature in the room.
R
Input Register
00102
val_u1
1 IDLE
2 HEATING
3 COOLING
4 BLOCKED_HEATING
5 BLOCKED_COOLING
00103
R
Input Register
val_u1
Please check top of the document - GENERAL BLOCKING SOURCES
R
Input Register
00104
val_d2_fp100
Current air temperature measured in the room.
R
Input Register
00105
val_d2_fp100
Current floor temperature measured in the room.
R
Input Register
00106
val_d2_fp100
Current humidity measured in the room.
R
Input Register
00107
val_d2_fp100
Current calculated dewpoint
R
Input Register
00111
val_u1
0 .. NONE
73 .. ITC1 (Address of modbus object)
74 .. ITC2 (Address of modbus object)
77 .. HCC1 (Address of modbus object)
78 .. HCC2 (Address of modbus object)
79 .. HCC3 (Address of modbus object)
81 .. H/C Source (Address of modbus object)
R
Input Register
00112
val_u1
0 .. NONE
73 .. ITC1 (Address of modbus object)
74 .. ITC2 (Address of modbus object)
77 .. HCC1 (Address of modbus object)
78 .. HCC2 (Address of modbus object)
79 .. HCC3 (Address of modbus object)
R
Input Register
00114
val_u1
0 .. NONE
650 .. AHU 1 (Address of modbus object)
651 .. AHU 2 (Address of modbus object)
652 .. AHU 3 (Address of modbus object)
653 .. AHU 4 (Address of modbus object)
R
Input Register
00115
val_u1
0 .. NONE
650 .. AHU 1 (Address of modbus object)
651 .. AHU 2 (Address of modbus object)
652 .. AHU 3 (Address of modbus object)
653 .. AHU 4 (Address of modbus object)
R
Input Register
00117
val_u1
0 NONE (not used in this room or load was not detected on at least one output)
1 IDLE
2 HEATING
3 COOLING
4 BLOCKED_HEATING
5 BLOCKED_COOLING
R
Input Register
00118
val_u1
0 NONE (not used in this room or load was not detected on at least one output)
1 IDLE
2 HEATING
3 COOLING
4 BLOCKED_HEATING
5 BLOCKED_COOLING
00119
R
Input Register
val_u1
0 NONE (not used in this room)
1 IDLE
Address space version
2.0
3.0
3.1
3.1
FW 6
FW 8
FW 10
FW 12
YES
YES
YES
YES
YES
YES
YES
YES
YES
CHANGED
CHANGED
YES
YES
YES
YES
CHANGED
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
CHANGED
CHANGED
YES
YES
YES
CHANGED
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
EXTENDED
YES
YES
-
YES
YES
YES
-
-
YES
YES
-
-
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
YES
YES
YES
-
-
YES
YES
-
-
-
YES
-
-
-
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
EXTENDED
YES
YES
YES
YES
EXTENDED
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
-
YES
CHANGED
YES
-
YES
CHANGED
YES
-
-
YES
YES
-
-
YES
YES
-
-
YES
YES
-
-
YES
YES