Herunterladen Diese Seite drucken

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Technical datas

The power supplies and electrical control equipment are to be operatetd exclusively with the components authorised by
the manufacturer.
Electrical properties
Rated operating voltage:
Alarm indicator:
Operating current at 30 V, quiescent:
Operating current at 30 V, alarm:
Permissible voltage range:
Signal transmission:
Remote indicator, short circuit proof:
Mechanical properties
Dimensions:
Weight:
Installation and ambient conditions
Monitored area¹:
Mounting height¹:
Permissible air speeds:
Ambient temperature:
Ambient conditions for moisture (constant,
without condensation) at ≤ 34 °C:
Ambient conditions for moisture (constant,
without condensation) at > 34 °C:
Authorisations and certifications
Standards:
Degree of protection IEC 529:
Approval VdS:
Approval CPD:
Material
Housing:
Colour:
Trouble-free and safe operation is only warranted when used in conjunction with appropriate manufacturers control unit.
Request a technical conformity declaration when using drives from other manufacturers.
¹ Values dependent on the ceiling design (height, inclination) according to project guidelines that are specific to each
country.
03/24999571
Scattered light smoke detector MSD 523
24 V DC
LED red
max. 120 μA
min. 19 to max. 22.5 mA
18 to 30 V DC
current rise
max. 5 mA
see pages 7
125 g
max. 150 m²
max. 16 m
max. 20 m/s
-25 °C to +60 °C
10 - 95 %, relative humidity
max. 35 g/m³, min. 10 %, relative humidity
EN 54-7
IP 44
G 207123
0786-CPD-20330
ABS/PC
electro white
9

Quicklinks ausblenden:

Werbung