Herunterladen Inhalt Inhalt Diese Seite drucken

Open Window Detection - Watts Vision WT-D03 Benutzerhandbuch

Vorschau ausblenden Andere Handbücher für Vision WT-D03:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 68
14
Calibration of external room sensor (remote)
This menu is only displayed if parameter rEG (#20) is set with
"Amb" or "Flr" or "Fll".
Calibration must be done after a given order has been
operating for a day. Place the thermometer in the middle
of the room at about 1.5 m above the floor. Record the
temperature shown after 1 hour. When you enter calibration
mode, displaying of
performed yet. Enter the reading on your thermometer using
minus
and plus
The setting is validated with validation key.
indicate that calibration.
If user press simultaneously minus
sensor calibration is reset.
Important note: a large temperature deviation may indicate an
inappropriate installation of the thermostat. If the temperature
difference is too big, this could mean your thermostat was not
installed properly e.g. in the right place.
When user changes this parameter, regulation will restart.
Default value: 0.0°C

Open window detection

"Yes": activation of function
"no": no activation
If function is active, logo
More information is in paragraph "Opened window detection"
Default value: Yes
Operating mode of thermostat
- Hot: heating mode
- CLd: cooling mode
- Aut: automatic mode
- Rev: displaying of reversible menu (see paragraph 5.6
"Reversible mode")
Default value: Hot
Authorization or not of cooling mode
This parameter menu allows to enable or disable cooling in
specific room like bathroom.
When the system is in cooling mode, the thermostat is
switched in Off mode.
Default value: Yes
logo means no calibration has been
keys (step of 0.1°C).
and plus
logo disappears.
Range value: -5.0°C to 5.0°C
Values: Yes / no
Values: Hot / Cold / Aut / Rev
Other value: no
EN
logo appears to
keys,

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis