(1)
Room A
12:00
Test
Cool
Mode
Fan Speed
(2)
Room A
12:00
Test
(3)
Test mode
Test mode stop.
Return
Yes
No
Measures when a check code "E18" appears at the time of simultaneous
(twin, triple, or double twin) connection
1
Reconnect the wires between indoor unit and indoor unit correctly.
Incorrect connection
A
A
B
B
1
2
3
1
2
3
Indoor unit
1
2
3
Outdoor unit
Disconnect the
connection
-
between indoor units.
2
Change each indoor unit into correct address.
• Change the address of each indoor unit into correct one according to "Manual address setup procedure" in
the previous page when the check code "E18" appears on the remote controller.
143-EN
4
Push the [
ON / OFF] button to start the
test mode. The screen (1) shown in the left
appears. (The screen (2) appears when the
operation is stopped.)
Perform the test mode in the "Cool" or "Heat"
mode.
Temperature setting cannot be adjusted during
the test mode.
Check codes are displayed as usual.
5
When the test mode is finished, push the
[
] / [
] button to select "1. Test
mode" on the "Field setting menu" screen,
then push the "
Set
button.
The screen (3) appears.
Pushing the "
Yes
stops the test mode screen and continues the
normal operation.
NOTE
The test mode stops after 60 minutes and the screen
returns to the normal / detailed display.
Correct connection
A
A
B
B
1
2
3
1
2
3
Remote
controller
Indoor unit
1
2
3
Outdoor unit
 Monitor function
The sensor temperature or operational status of indoor unit, outdoor unit, or remote controller can be monitored.

Monitor function

Code
01
Return
1
Set" [
F2]
Push the [
menu screen.
2
Push and hold the [
Yes" [
F1] button
the [
display the "Field setting menu".
Push and hold the buttons for more than 4
seconds.
3
Push the [
"4. Monitor function" on the "Field setting
menu" screen, then push the "
Set" [
Push the [
the code to check data.
4
Push the [
the "Field setting menu" screen.
Remote
controller
– 72 –
Code
Data
0024
MENU] button to display the
MENU] button and
] button at the same time to
] / [
] button to select
*1 : Display and the contents
- - - - : Sensor function is not available.
Set
0000 : Normal
F2] button.
0001 : Sensor has been used for 5 years.
] / [
] button to select
0002 : Sensor trouble or exceeding the life of the
0003 : Sensor is detecting refrigerant leak
CANCEL] button to return to
*2 : The above temperature values are estimated from
the temperature of the heat exchanger. It may differ
from the actual discharge temperature.
Code
*3 : For outdoor unit data, refer to the Installation
Manual and Service Manual of the outdoor unit.
Indoor unit data
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
Indoor unit heat exchanger (coil)
03
temperature (TCJ)
Indoor unit heat exchanger (coil)
04
temperature (TC)
07
Indoor unit fan speed (×1 rpm)
Communication protocol
B9
(0000: TCC-Link, 0001: TU2C-Link)
Indoor unit fan cumulative operating hours
F3
(×1 h)
Indoor unit refrigerant leak detection sensor
E2
output *1
Indoor unit discharge air temperature (TF)
F8
*2
product for sensor
Outdoor unit data *3
Data name
Outdoor unit heat exchanger (coil)
60
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
Heatsink temperature (THS)
6A
Operating current (×1/10)
Outdoor heat exchange (coil)
6D
temperature (TL)
Compressor cumulative operating hours
F1
(×100 h)
144-EN