Herunterladen Inhalt Inhalt Diese Seite drucken

Pentax IPFC-Serie Betriebsanleitung Seite 24

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 86
Parameter
To ensure proper operation of pressure control is recommended to place the sensor near the pump.
To compensate the pressure loss in the pipes (proportional to flow) it is possible to vary the pressure set in a linear
relation with respect to frequency.
H
It can perform the following test to verify the correct value of compensation:
1. install a pressure gauge away from the pressure sensor
2. open completely the valve
3. check the pressure gauge
--> Set the value of compensation. equal to the difference of the values from the two gauges.
When using a group of pumps, the pressure compensation to be applied to each pump is equal to the total pressure
compensation (when all the pumps are running at full speed) divided by the number of pumps in the group.
Operating freq.
XXX [Hz]
Operating freq. 2
XXX [Hz]
Freq.min.control
XXX [Hz]
Stop delay
XX [s]
Control ramp
XXX.X [s]
24
Default
Pressure
sensor
Min mot. freq.
50
Frequency value to feed the pump.
50
Frequency value to feed the pump.
Minimum frequency below which the
50
pump tries to stop.
Delay for which the pump tries to stop
5
below freq.min.control.
Ramp time from freq.min.control to
min.motor freq. If, during this time, the
20
read value goes below the (set value -
delta control), IPFC powers the motor
again; otherwise, IPFC will stop the pump.
Description
300 m
Compensation (1 bar)
Set value (3 bar)
Max mot. freq.
4 bar
Q

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für Pentax IPFC-Serie

Inhaltsverzeichnis