4. ELECTRICAL WIRING

4-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely
following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each
unit, and a power supply disconnect and circuit breaker for
overcurrent protection should be provided in the exclusive
line.
(3) To prevent possible hazards from insulation failure, the unit
must be grounded.
(4) Each wiring connection must be done in accordance with
the wiring system diagram. Wrong wiring may cause the
unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very
dangerous. The manufacturer will accept no responsibility
for any damage or misoperation that occurs as a result of
such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant
rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as follows:
● The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
● Use shielded wires for inter-unit control wiring between units
and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop designated by the
manufacturer, because special-purpose tools are required.
All manuals and user guides at all-guides.com
14
4-2. Recommended Wire Length and Wire Diameter
for Power Supply System
Indoor unit
(B) Power supply
Type
K1
Max. 150 m
Control wiring
(C) Inter-unit
(between outdoor
(D) Remote control
and indoor units)
control wiring
2
0.75 mm
0.75 mm
(AWG #18)
(AWG #18)
Use shielded wiring*
Max. 1,000 m
Max. 500 m
N OT E
*
With ring-type wire terminal.
Time delay fuse or
circuit capacity
2
2.5 mm
10-16 A
(E) Control wiring
wiring
for group control
2
2
0.75 mm
(AWG #18)
Max. 200 m (Total)