Technical Data

CAUTION! Risk of damage!
Inappropriate transport and interim
storage can cause damage to the
product. The unit must be protected
from moisture, frost and mechanical
damage during transport and interim
storage.
4

Intended use

The condensate lifting unit serves as a compo-
nent in installations for pumping accumulated
condensate. The condensate lifting unit works
automatically and is ready for connection. It is not
intended for installation in gas condensing boilers
with a condensate pH value of 2.5 or higher.
5
Technical Data
General Data
Connected voltage / Frequency
Connecting cable
Connected load / Nominal current
Insulation class
Protection class
Duty Type
Alarm contact
Permissible fluid temperature
Approved medium
Delivery head / delivery rate
Sound pressure level
Tank volume
Weight approx.
Dimensions
Inlet connections
Discharge connection
3
CAUTION! Risk of damage!
If the condensate lifting unit is being
used in gas-fired boilers with an out-
put of > 30kW, or in oil-fired boilers in
general, a neutralisation unit must be
installed upstream of it.
The condensate lifting unit is not designed to be
used by persons (including children) with impaired
physical, sensory or mental capabilities or who
have insufficient experience or knowledge to op-
erate the unit.
Any such use is considered outside the intended
use.
1~230V / 50Hz
Mains cable: 2m
Alarm signal: 2m
60W / 0.6A
B (130°C)
IP 20
S3 30%
(Intermittent operation: 3 min. operation - 7 min.
pause)
~230V / 1A
COM = white, NC = red, NO = black
max. 50°C
Condensate water, pH > 2.5
max. 5.5m / 190L/h
< 50dBA at 1m
1.2L
2.1kg
Width: 210mm
Height: 120mm
Depth: 167mm
Diameter: 30mm
Diameter: 19mm
Diameter: 10mm