Ferngesteuerte lastumschalter
Inhaltsverzeichnis

Werbung

3.2. Quick Start ATyS d M (4P)
quick start
40 - 160A (4P)
EN
ATyS
d
Remotely Operated
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
Packaging and contents are in good condition.
n
The product reference corresponds to the order.
n
Contents should include:
n
Qty 1 x ATyS M
Qty 1 x Emergency handle extension rod
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
This product must always be installed and commissioned
n
by qualified and approved personnel.
Maintenance and servicing operations should be
n
performed by trained and authorised personnel.
Do not handle any control or power cables connected to
n
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
Always use an appropriate voltage detection device to
n
confirm the absence of voltage.
Ensure that no metal objects are allowed to fall in the
n
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
In case the product is dropped or damaged in any way it
n
is recommended to replace the complete product.

Accessories

Bridging bars 125A or 160A.
n
Control voltage transformer (400Vac -> 230Vac).
n
Voltage sensing and power supply tap.
n
Terminal shrouds.
n
Additionnal aux contact block.
n
Polycarbonate enclosure.
n
Polycarbonate extension box.
n
Dual Power Supply (DPS).
n
Power Connection Terminals.
n
ATS Control relay ATyS C30 + D10 or D20.
n
ATS control relay ATyS C20.
n
ATS control relay ATyS C40.
n
www.socomec.com
www.socomec.com/operating-instructions
To download, brochures, catalogues and technical manuals.
Printing informations: 1 color Black. White paper 90g/m
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
CORPORATE HQ CONTACT:
SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE
Non contractual document.
542928E
Subject to change without notice.
10
DE
Installation and Commissioning
M
STEP 1
Cabinet / Back
Plate Installation
STEP 5B
• Open the front cover as
shown to put into manual
mode.
• Use the handle situated in
the front panel under the cover to operate the
transfer switch.
• Check the changeover switch position on the
indicator before operating.
90º
90º
To simplify operation
use the handle with the
extension provided.
STEP 5C
• In order to padlock put the
product in manual mode.
• Pull the locking mecha-
nism and insert a padlock
as shown.
• As standard padlocking in the 0 position.
2
.
Configurable to I-0-II (see step 1).
1x 4-8 mm
STEP 2
STEP 3
STEP 4
Connecting the
CONTROL /
CHECK
POWER section
AUX POWER
terminal
connections
STEP 4
Manual operation
Whilst in manual mode, check the wiring and
if ok power up the product.
STEP 5A
Extension
Close the front cover as shown to put the product
into automatic mode. The product is now ready to
receive order inputs based on the following logic.
(Max 8 Nm)
order I
order 0
Padlocking mode
order II
position I
position 0
position II
Note: Excludes position switching delays.
For contactor logic bridge
contact 313 with 317.
To operate: close the
contact corresponding to
the desired position.
STEP 5A
Control by an external
order (AUTO)
STEP 5B
Emergency Manual
Operation
STEP 5C
Padlocking
2 clips de verrouillage
Check
Automatic operation
Impulse logic
Contactor logic
Imp. ≥60ms
maintened
ATyS d M – 542929D – SOCOMEC
ST
Recom
Reco
DIN
IEC
ST
It
te
b
Source
STEP 3
CONTR
Termin
Ensure that the product is in Ma
0,5 to 2,5
#28 to #14
0,5 to 2,5
II
#28 to #14
6 mm /
Slotted hea
o
I
Auxiliary contacts:
One module
1309 1001
Fitting of the 2nd AC:
To fit an AC, the switch must first be
one NO/NC changeover contact for e
with the module.