Herunterladen Inhalt Inhalt Diese Seite drucken

socomec ATyS d M Installationshandbuch Und Bedienungsanleitung Seite 11

Ferngesteuerte lastumschalter
Inhaltsverzeichnis

Werbung

STEP 1
Installation
Caution: Ensure that the product is installed on a flat rigid surface.
Recommended orientation
OK
OK
OK
Recommended
DIN RAIL
IEC 60715
STEP 2
Power Terminal Connections
It is essential to tighten all used
terminals, with cables and/or
bridging bars, before use.
Source supply side
STEP 3
CONTROL / AUX POWER
Terminals and wiring
2
0,5 to 2,5 mm
#28 to #14 AWG
0,5 to 2,5 mm
2
#28 to #14 AWG
6 mm / 0,236"
Slotted head 2,5 mm
One module factory fitted (1309 1001 ).
1309 1001 or 1309 1011
Use 35mm
screws for
2 modules
ATyS d M – 542929D – SOCOMEC
13
26
OK
OK
OK
OK
OK
OK
OK
OK
OK
Ok
Ok
Ok
movement on the DIN rail.
Load side
bridging bar.
125A: 1309 4006
160A: 1309 4016
Hexagonal Metric
Allen size 4
10 to 70 mm
2
5,0 Nm
# 8 to # 00 AWG
*
6 to 70 mm
2
# 10 to # 00 AWG
15 mm / 0,59 "
10 to
70 mm²
15mm
Hexagonal Metric
Allen size 4
44,1 lb-in 5,0 Nm
Type
Inputs
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
Slotted head 3mm 0,5 Nm
Auxiliary
contacts
unit.
A
!
Pozidriv PZ2 - 1 Nm
340
324
116
18
MAX : 2
OK
OK
OK
OK
OK
OK
Ok
Ok
46
53
73,5
Tighten to avoid
52
6 mounting brackets
Posidriv PZ1
6x M6 screw - 2,5 Nm
1 Nm
Voltage taps provide 2x ≤ 1.5mm
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
!
X8
Terminal no.
Description
101 / 102
Source 1 power supply
201 / 202
Source 2 power supply
313
Position 0 order if closed with 317.
Also allows control logic selection: contactor
(always closed) / impulse (close to switch)
314
Position II order if closed with 317
315
Position I order if closed with 317
317
Common control terminal for 313 to 315
11/12/14
Position I
21/22/24
Position II
01/02/04
Position 0
Control of position I and II have priority on control of position 0.
LOAD
B
B
B
B
317
315
314
313
202
6
6
6
6
1
3
2
340
324
116
13
26
18
MAX : 2
340
326
104
176
OK
STEP 1
Posidriv PZ2
OK
STEP 2
connections.
2
!
STEP 1
10 to 70 mm
2
# 8 to # 00 AWG
*
6 to 70 mm
2
# 10 to # 00 AWG
15 mm / 0,59 "
Hexagonal Metric
OK
Allen size 4
!
44,1 lb-in 5,0 Nm
X8
STEP 2
STEP 1
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
Posidriv PZ2
0,5 to 1,5 mm²
6 mm
2 X
STEP 2
Characteristics
220Vac -20% (176Vac) to 240Vac
+20% (288Vac) 45 to 65Hz
Do not connect to any power supply
Dry potential free contact
250Vac 5A AC1
24Vdc 2A
1: Position I order
2: Position II order
3: Position 0 order
4: Power supply I (230 VAC)
5 A AC1
5 A AC1
5 A AC1
5 A AC1
250 Vac
250 Vac
250 Vac
250 Vac
5: Power supply II (230 VAC)
22 24 21
22 24 21
22 24 21
22 24 21
6: Voltage tap
7: Auxiliary contact block -
1 NO/NC contact per position I,
7
0, II (1x factory fitted )
11 14 12
11 14 12
11 14 12
11 14 12
A: Bridging bar (accessory)
01 04 02
01 04 02
01 04 02
01 04 02
B: Single-phase voltage sensing tap
1309 1001
1309 1011
(accessory)
C: F1/F2 = fuse 10 A gG
201
102
101
C
5
* Remote orders from ATS
4
controller such as ATyS C20/
C30/C40 or PLC, BMS, etc.
!
Padlocking configuration
The ATyS M is delivered with
padlocking configured to the
O position.
OK
!
46
53
73,5
Posidriv PZ2
STEP 1
STEP 3
!
!
Posidriv PZ2
!
Posidriv PZ2
2 X
STEP 3
STEP 2
STEP 4
To allow padlocking in all
Posidriv PZ2
positions (I - O - II), configure
OK
2,2 lb-in 0,25 Nm
OK
the ATyS M as follows before
installation. (Screw is located
2 X
at the back of the product).
STEP 4
Posidriv PZ2
Posidriv PZ2
Step 1
STEP 1
STEP 3
!
OK !
STEP 1
STEP 3
Posidriv PZ2
STEP 3
Posidriv PZ2
Posidriv PZ2
2x
2 X
Posidriv PZ2
2 X
Posidriv PZ2
2,2 lb-in 0,25 Nm
Step 2
STEP 2
STEP 4
STEP 2
STEP 4
2 X
OK !
OK !
STEP 4
Posidriv PZ2
OK !
Step 3
2x
STEP 3
Posidriv PZ2
2,2 lb-in 0,25 Nm
Recommanded
STEP 4
connection
cross-section
OK !
0,5 to 2,5 mm²
(rigid)
0,5 to 1,5mm²
(stranded)
DE
Posidriv PZ2
2,2 lb-in 0,25 Nm
OK !
Posidriv PZ2
Posidriv PZ2
2,2 lb-in 0,25 Nm
2,2 lb-in 0,25 Nm
11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis